24
PAV LAN
DC Power Page
3. Webpage
Protection tab
Click the Protection tab on the DC Power page. You can set the four protection functions
shown in the following table. However, in a multi-drop connection, the settings are applied
only to the PAV selected from the Multi-Drop RS-485 Address list box.
Protection tab
4
1
2
3
No. Item
Description
1
Over-Voltage
Protection
Enter a new value in New Setting and click Apply to change the over-
voltage protection setting.
Set to Maximum: The value is set to the maximum value that can be
set.
Set to value: The value is set to the value that you enter.
2
Under-Voltage
Protection
Enter a new value in New Setting and click Apply to change the under-
voltage protection setting.
Set to Zero: The value is set to zero.
Set to value: The value is set to the value that you enter.
3
Foldback Protection
CV: Activated when switching from CC to CV mode.
CC: Activated when switching from CV to CC mode.
OFF: Not activated regardless of the switching between CV and CC
modes.
4
Auto Start Setting
Safe start: The output is off when the PAV starts.
Auto start: When the PAV starts, the output is in the state that it was in
immediately before the AC input was turned off.