OT01-PCR-LA/2
Maintenance 7-5
7.2.2
Single-phase, Three-wire Operation
Symptom1: The PCR-LA power supply display panel displays
“Err2” or nothing, or continues to display the version
number.
Symptom2: The rated output cannot be generated.
Check item
Possible cause
Remedy
Location and condition
of the item concerned
Check results
Check whether the single-
phase, three-wire cards
are properly inserted into
the correct slot.
No
Improper phase-card
installation
Insert the card(s) into the correct
slot(s). See “2.5.5 Single-phase,
Three-wire Output Driver”.
Check whether the drive-
signal cables are properly
connected.
No
Improper drive-sig-
nal cable connection
Securely connect the cables
between the master and slave units.
See “2.5.5 Single-phase, Three-
wire Output Driver”.
Check item
Possible cause
Remedy
Location and condition
of the item concerned
Check results
Check whether the out-
put neutral point is con-
nected to a load (single-
phase, three-wire sys-
tem).
No
A load is connected in
a single-phase, three-
wire system (delta
connection). In delta
connection, the pres-
ence of unbalance
between three-wire
currents may disable
the generation of
rated output.
Connect the output neutral point to
the load (single-phase, three-wire
system).
Содержание OT01-PCR12000LA/2
Страница 10: ...VIII Contents OT01 PCR LA 2 ...
Страница 16: ...1 6 General OT01 PCR LA 2 ...
Страница 44: ...2 28 Installation and Preparation for Use OT01 PCR LA 2 ...
Страница 56: ...4 8 Part Names and Functions OT01 PCR LA 2 ...
Страница 64: ...5 8 Single phase Parallel Operation OT01 PCR LA 2 ...
Страница 82: ...6 18 Single phase Three wire Operation OT01 PCR LA 2 ...
Страница 94: ...1 2 Index OT01 PCR LA 2 ...
Страница 95: ......
Страница 96: ...OUTPUT EXPANSION KIT OT01 PCR LA 2 OPERATION MANUAL ...