Single-phase, Three-wire Operation 6-3
■
Limitations in the line voltage display mode
•
Voltage can be set as line voltage. V-phase voltage cannot be set individually.
•
Output power cannot be measured.
6.3
Output Voltage Setting
Phase voltage setting
When the phase voltage is set on the U-phase unit, the phase voltages of the other
phase unit is also set to the same value. U-phase unit setting has precedence over
unit settings of the V-phase.
If the phase voltage is individually set on the V-phase unit, only the V-phase voltage
is set. Then, if the phase voltage is re-set on the U-phase unit, the phase voltage of
the V-phase unit becomes the same as the phase voltage of the U-phase unit (the U-
phase unit has precedence over the V-phase unit).
Individual voltage setting on the V-phase unit requires that the relevant PCR-LA
power supply be in the phase voltage display mode.
• The phase voltage is 1/2 of the line voltage.
Line voltage setting
Set the line voltage on the U-phase unit. The line voltage cannot be set on the V-
phase unit.