11
Operation
Type 8615500120-000 / 8615500130-000
Input data for set-point value signal
0/4 ... 20 mA:
Input resistance 180
Ω
Resolution
12 bit
0 ... 5/10 V:
Input resistance 19 k
Ω
Resolution
12 bit
Analogue feedback
Max. current
10 mA
(for voltage output 0 ... 5/10 V)
Burden (load)
0 ... 560
Ω
(for current output 0/4 ... 20 mA)
Inductive
proximity switches
100 mA current limitation
Binary outputs
galvanically isolated, PNP
Current limitation
100 mA, output is clocked if overload
occurs
Binary input
galvanically isolated, PNP
0 ... 5 V = log "0", 10 ... 30 V = log "1"
inverted input in reverse order
(input current < 6 mA)
Communication
interface
Direct connection to PC via USB adapter
with integrated interface driver, commu-
nication with communications software
based on FDT/DTM technology.
7
operaTion
7.1 description of the operating and
display elements
operating elements:
Abbreviated designation for the
displayed process value
Process value
*
Unit of the displayed process
value
Designation for the function of
the keys
Right selection key
Arrow key , arrow down
Arrow key , arrow up
Left selection key
display elements of the process level:
Save symbol
Symbol for position control
Symbol for process control
Symbol for the AUTOMATIC operating state
Other symbols are displayed according to the activated func-
tions. See operating instructions type 8615500120-000 /
8615500130-000
Fig. 4:
Display elements of the process level; operating elements