12.2 Rotary valve
The stop position feedback signal valve "OPEN" or "CLOSED" is carried out contactlessly over the
magnetic field of the bar magnets in the pulse generator during overlap with the hall sensors on the
printed circuit board.
Valve Position Indicator
➣
ELECTRICAL - through the DUO - LED on the board
• valve ’’OPEN’’= Signal DUO-LED GREEN
• valve ’’CLOSED’’= Signal DUO-LED RED
➣
MECHANICAL - through the position of the spindle
• valve ’’OPEN’’= Valve position indicator points in flow direction
• valve ’’CLOSED’’= Valve position indicator points crosswise in flow direction
Ventilstellungsanzeige