Technical Data Sheet 2.50-35.021-01-en Rev
D e v i ce De s c ri p ti on
FSM21 Front Switch Module
For connection to the FBM38 fieldbus module.
A
M
acro Function
The functions of the two 2 or 1-stage device controls are made by assigning macro 21 on the FBM38 fieldbus
odule.
m
Using the macro function, relay outputs K1/K2 and K3/K4 are each controlled on the FBM38 with 2-stage control.
Depending on the switch setting, the relays lock against each other or switch together. A mechanical limitation of the
switch positions can be made by attaching switch stop rings (see the “Switch stop” section).
A
load/rolling switch with different switching delays can be set in macro 21.
Binary inputs 55/IN–58/IN on the FBM38 are defined as malfunction messages by the macro function, and are
hown on the signal LEDs (1.3/1.4, 2.3/2.4) on the FSM21.
s
Depending on the operating mode set on the FBM38 ( / ), the following is signaled by the signal LEDs (1.1/1.2,
.1/2.2):
2
Binary inputs 51/IN–54/IN as operating messages (“Remote” operating mode )
The status of relay outputs K1–K4 on the FBM38 (“Local” operating mode )
A
ll macro settings are made on the FBM38 fieldbus module.
The FBM settings and a detailed macro description are found in technical data sheets 2.50-30.038-01-en and
2.50-30.038-02-en. Both of these are included with the FBM38
fieldbus module.
Function/Operation
Manual/automatic switch 1
Switch positions:
– Automatic operation, relay K1 and K2
– Off, relay K1 and K2
– On, level 1.1
(FBM38 relay output K1)
– On, level 1.2
(FBM38 relay output K2)
Signal LED 1.3:
Malfunction
message
(FBM38 input 55/IN)
Signal LED 1.4:
Malfunction
message
(FBM38 input 56/IN)
Signal LED 2.3:
Malfunction
message
(FBM38 input 57/IN)
Signal LED 2.4:
Malfunction
message
(FBM38 input 58/IN)
Manual/automatic switch 2
Switch positions:
– Automatic operation, relay K3 and K4
– Off, relay K3 and K4
– On, level 2.1
(FBM38 relay output K3)
– On, level 2.2
(FBM38 relay output K4)
Signal LED 1.1:
Operational feedback, level 1.1, on/off
(FBM38 input 51/IN;
Relay output K1 on/off)
Signal LED 1.2:
Operational feedback
,
level 1.2, on/off
(FBM38 input 52/IN;
Relay output K2 on/off)
Signal LED 2.1:
Operational feedback, level 2.1, on/off
(FBM38 input 53/IN;
Relay output K3 on/off)
Signal LED 2.2:
Operational feedback
,
level 2.2, on/off
(FBM38 input 54/IN;
Relay output K4 on/off)
Note
Only the green LEDs (1.1, 1.2, 2.1 and 2.2) can be switched off. The red LEDs (1.3, 1.4, 2.3 and 2.4)
cannot be configured.
Page 6 / 12