LaserNET Program User's Guide
September 2003
TM0048
6-5
Note:
If the Detector is isolated and the actual smoke level is above programmed thresholds, care must
be taken before the Detector is de-isolated. If the actual smoke level is above a programmed
threshold when the Detector is de-isolated, the Detector will immediately go into alarm. LaserNET
will display a de-isolation warning (see Figure 6-6).
Figure 6-6. De-Isolation Warning Message
6-4.4
Reset
Selecting
<Reset>
resets any latched alarm or fault conditions on the Detector if the conditions have cleared.
6-5
CONFIGURING A DETECTOR
When a Detector is installed, it must be configured for proper operation. A Detector will arrive with its
configuration preset to certain factory default values; these are shown in Table 6-1 (for the IIM and Direct
Connection).
6-5.1
Owner Location
This feature is used only when connected to an IIM. It is used to program the location as seen in the banner
of the Display and Control Window. Note that Location is distinct from Address which is configured else-
where.
1. Select
Options>Configure>Owner Location
. The screen shown in the following figure will open.
Figure 6-7. Owner Location Window
2. The location of the Detector (if entered) is displayed in the window. Enter a new location name up to 20
characters long.
3. Select
<OK>
to save the configuration.
4. The owner location, along with the address in parentheses, will now be displayed in the title bar of the
Display and Control window.
Содержание HART XL
Страница 2: ......
Страница 4: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 6: ...ii September 2003 TM0048 LaserNET Program User s Guide THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...1 6 September 2003 TM0048 LaserNET Program User s Guide THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 28: ...3 6 LaserNET Program User s Guide September 2003 TM0048 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 60: ...TM0048 LaserNET Program User s Guide September 2003 6 22 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 75: ......