TM0048
LaserNET Program User's Guide
September 2003
6-14
Note:
If Load Configuration is selected or an alarm condition occurs while Auto-Setup is enabled, LaserNET
will abort the Auto-Setup function. An existing alarm, pre-alarm, fault or isolate condition will prevent
the execution of Auto-Setup.
6-5.8
Display Enable
Connect the Display Module to the Detector.
1. Select
Options>Configure>Display Enable
. Figure 6-14 displays.
Figure 6-14. LCD Enable Screen
Enable Display
Check
Enable Display
and click on the
<OK>
button. If the LCD isn't connected, a
warning message will appear. Recheck hardware configuration and repeat the step.
Sounder Configuration
Select
Alarm
to set the Detector to have sound only in an Alarm condition,
Pre-Alarm box to set the Detector sound only in a Pre-Alarm condition, or the Fault box for the Detector
to sound only for fault conditions.
Display Module Units
This function controls the numeric display on the Detector. Select either
Metres
or
Feet
.
6-5.9
Display Passwords
This feature allows the display module password to be modified via LaserNET. Enter in the new password(s)
(must be from two to eight numeric characters ranging from 0-9) and click
<OK>
.
Figure 6-15. Display Passwords Screen
Содержание HART XL
Страница 2: ......
Страница 4: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 6: ...ii September 2003 TM0048 LaserNET Program User s Guide THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...1 6 September 2003 TM0048 LaserNET Program User s Guide THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 28: ...3 6 LaserNET Program User s Guide September 2003 TM0048 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 60: ...TM0048 LaserNET Program User s Guide September 2003 6 22 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 75: ......