2 / 3 

 

P/N 3102359-EN • REV 002 • ISS 21OCT20 

Figure 2: Mounting diagram 

 

(1)  Compatible electrical box 

(2)  FX-T3T4 

(3)  #6-32 × 1/2 screws (2X) 

(4)  Wall plate 

(5)  Cover plate plastite screws (2X) 

Applications 

For sounder base applications, refer to the sounder base installation 

sheet for details.  

Figure 3: Wiring Diagram 

 

Maintenance 

For Canadian installations, follow CAN/ULC-S536 

Standard for the 

Inspection and Testing of Fire Alarm Systems

Wiring 

Wire the FX-T3T4 as shown in Figure 3 below. For further wiring 

details, refer to 

FX-64 and FX-1000 Technical Reference Manual

 

(P/N 3102352). 

Note: 

T3T4+ connects to the SIG– terminal on the sounder base and 

T3T4– connects to the SIG+ terminal. The FX-NAC is required for 

circuit supervision and is ordered separately. 

Figure 3 Legend 

(1)  AUX riser from previous device. Use a power-limited and regulated 

24 VDC primary or auxiliary power supply that is UL/ULC Listed for 

fire protective signaling systems. 

(2)  AUX riser to the next FX-T3T4 in the same notification zone or to 

the Class A return on the power supply.  

(3)  Signaling line circuit from previous device. 
(4)  Compatible sounder base. 
(5)  Signaling line circuit to next device. 

(6)  In order to have a Class A T3T4 riser, wire the SLC as Class A 

and limit the AUX input connection to the same room, within 20 ft. 

(6.1 m), and enclose in conduit or equivalent protection against 

mechanical injury. 

(7)  No connection. Do not connect notification appliances. 
 

 

 

(5)

(4)

(3)

(2)

(1)

TB1

TENS

ONES

TB2

12

11

10

9

4

3

2

1 0

8

5 6 7

0 9

1

8

2

7

3

6

4 5

+
+

SLC+

SLC–

AUX+

AUX–

(3)

(1)(6)

(4)

TB1

TENS

ONES

TB2

12

11

10

9

4

3

2

1 0

8

5 6 7

0 9

1

8

2

7

3

6

4 5

+

+

47 k  EOLR

Ω

FX-NAC

FX-T3T4

(4)

T3T4+
T3T4–

T3T4+
T3T4–

N.C.
N.C.

SLC+
SLC–

AUX+

AUX–

(2)

(5)(6)

(7)

firealarmresources.com

Отзывы: