After installation, TEST your alarm by pressing and holding the test button for
several seconds. This should sound the alarm.

4. OPERATION AND TESTING

OPERATION: The smoke alarm is operating once A.C. power is applied, fresh
batteries are installed and testing is complete. When the smoke alarm ionization
chamber senses products of combustion, the horn will sound a loud (85db) tem-
poral alarm until the sensing chamber is cleared of smoke particles.

LED INDICATORS: This smoke alarm is equipped with red and green LED indica-
tors. The green LED is located under test button "B" and will be illuminated
when AC power is present. The red LED is located under test button “A”.

Standby:

The red LED will flash briefly approximately every 30- 40 seconds to 
indicate that smoke alarm is operating properly.

Alarm 

When the unit senses products of combustion and goes into alarm, 

mode:

the red LED will flash rapidly (one flash per second). The rapid 
flashing LED and temporal alarm will continue until the air is 
cleared.

WHEN UNITS ARE INTERCONNECTED, only the red LED of the alarm, which
senses the smoke or is being tested (the originating unit) will flash rapidly.  All
other units in the interconnect system will sound an alarm but their red LED's
will NOT flash rapidly.

Sensitivity

The red LED will be on while Test "B" button is being pressed.

test:

Alarm

This smoke alarm is equipped with an alarm memory, which 

Memory:

provides a visual indication when an alarm has been activated. 
The red LED will illuminate for about 1.5 seconds every 16 seconds 
to indicate the memory condition. The memory will remain activated 
until pushing the test button resets it. The memory will also reset if 
the battery voltage drops to 8 volts.

In an interconnected installation only the memory of the originating alarm will
be activated.

Содержание 1296

Страница 1: ...specified manufacturer s interconnect system or connection with non specified equipment from another manufacturer into an existing Kidde system could result in nuisance alarming failure to alarm or da...

Страница 2: ...THIS MANUAL NEAR THE ALARM FOR FUTURE REFERENCE CONTENTS OF THIS MANUAL 1 RECOMMENDED LOCATIONS FOR SMOKE ALARMS 2 LOCATIONS TO AVOID 3 INSTALLATION INSTRUCTIONS 4 OPERATION AND TESTING 5 NUISANCE AL...

Страница 3: ...details see MOBILE HOME INSTAL LATION below When mounting an alarm on the ceiling locate it at a minimum of 4 10 cm from the side wall see Figure 1 When mounting the alarm on the wall use an inside w...

Страница 4: ...ional protection see SINGLE FLOOR PLAN in Figure 2 WARNING TEST YOUR SMOKE ALARM OPERATION AFTER R V OR MOBILE HOME VEHICLE HAS BEEN IN STORAGE BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING USE 2 L...

Страница 5: ...ave inverter These types of inverters are sometimes used to supply power to the structure in off grid installations such as solar or wind derived power sources These power sources produce high peak vo...

Страница 6: ...nnected with other Kidde alarms and accessories as well as specified brands and models of interconnect compatible alarms Connection of Kidde products to a non specified manufac turer s interconnect sy...

Страница 7: ...ring the A C QUICK CONNECT harness as described in the WIRING INSTRUCTIONS attach the trim ring to the electrical box see Figure 5 3 Use a screwdriver to punch out only the pair of holes in the trim r...

Страница 8: ...m A C power TAMPER RESIST LOCKING PIN To make your smoke alarm tamper resistant a locking pin has been provided with your alarm Using this pin will help deter children and others from removing the ala...

Страница 9: ...en the unit senses products of combustion and goes into alarm mode the red LED will flash rapidly one flash per second The rapid flashing LED and temporal alarm will continue until the air is cleared...

Страница 10: ...ing instructions outlined in section 6 of the manual to clean your alarm To check for proper smoke entry into the alarm Kidde recommends using aerosol smoke manufactured by Home Safeguard Industries F...

Страница 11: ...he alarm see Section 3 Figure 6 BATTERY INSTALLATION AND REMOVAL To replace or install the batteries you must first remove the alarm from the trim ring by following the ALARM REMOVAL instruc tions at...

Страница 12: ...BER OPERATION THIS ALARM WILL CHIRP IF ABNORMAL OPERATION OF THE SMOKE SENSING CHAMBER IS DETECT ED THIS CHIRP WILL OCCUR APPROXIMATELY 10 SECONDS AFTER THE RED LED FLASH REPLACE THE ALARM IF THIS CON...

Страница 13: ...ooner than ionization alarms Home fires develop in different ways and are often unpredictable For maximum protection Kidde recommends that both Ionization and Photoelectric alarms be installed A batte...

Страница 14: ...y level of the home and in the kitchen basement and garage Know how to use a fire extinguisher prior to an emergency Current studies have shown smoke alarms may not awaken all sleeping indi viduals an...

Страница 15: ...iple station smoke alarms shall be installed as follows 1 In all sleeping rooms Exception Smoke alarms shall not be required in sleeping rooms in existing one and two family dwelling units 2 Outside o...

Страница 16: ...all rooms and areas of the household as follows A smoke alarm installed in each separate sleeping area in the vicinity of but outside of the bed rooms and heat or smoke detectors in the living rooms d...

Страница 17: ...E ALARM OR UNDER THE TERMS OF THIS LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACE MENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE SAFETY OR ANY OF ITS PAR ENT OR SUBSIDIARY CORPORATI...

Отзывы: