• Smoke alarms are not to be used with detector guards unless the combination

(alarm and detector guard) have been evaluated and found suitable for that
purpose.

3. INSTALLATION INSTRUCTIONS

WIRING REQUIREMENTS

• This smoke alarm should be installed on a U.L. listed or recognized junction

box. All connections should be made by a qualified electrician and all wiring
used shall be in accordance with articles 210 and 300.3(B) of the U.S. National
Electrical Code ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdic-
tion in your area. The multiple station interconnect wiring to the alarms must
be run in the same raceway or cable as the AC power wiring. In addition, the
resistance of the interconnect wiring shall be a maximum of 10 ohms.

• The appropriate power source is 120 Volt A.C. Single Phase supplied from a

non-switchable circuit which is not protected by a ground fault interrupter.

WARNING:

This alarm cannot be operated from power derived from a square

wave, modified square wave or modified sine wave inverter. These types of
inverters are sometimes used to supply power to the structure in off grid
installations, such as solar or wind derived power sources. These power
sources produce high peak voltages that will damage the alarm.

WIRING INSTRUCTIONS FOR A.C. QUICK CONNECT HARNESS

CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING
THE ALARM.

• For alarms that are used as single station, DO NOT CONNECT THE RED WIRE

TO ANYTHING. Leave the red wire insulating cap in place to make certain that
the red wire cannot contact any metal parts or the electrical box.

• When alarms are interconnected, all interconnected units must be powered

from a single circuit.

• A maximum of 24 Kidde devices may be interconnected in a multiple station

arrangement.  The interconnect system should not exceed the NFPA intercon-
nect limit of 12 smoke alarms and/or 18 alarms total (smoke, heat, carbon
monoxide, etc.).  With 18 alarms interconnected, it is still possible to intercon-
nect up to a total of 6 remote signaling devices and/or relay modules.

• When mixing models which have battery backup with models without battery

backup, be advised that the models without battery backup will not respond
during an AC power failure.

Содержание 1296

Страница 1: ...specified manufacturer s interconnect system or connection with non specified equipment from another manufacturer into an existing Kidde system could result in nuisance alarming failure to alarm or da...

Страница 2: ...THIS MANUAL NEAR THE ALARM FOR FUTURE REFERENCE CONTENTS OF THIS MANUAL 1 RECOMMENDED LOCATIONS FOR SMOKE ALARMS 2 LOCATIONS TO AVOID 3 INSTALLATION INSTRUCTIONS 4 OPERATION AND TESTING 5 NUISANCE AL...

Страница 3: ...details see MOBILE HOME INSTAL LATION below When mounting an alarm on the ceiling locate it at a minimum of 4 10 cm from the side wall see Figure 1 When mounting the alarm on the wall use an inside w...

Страница 4: ...ional protection see SINGLE FLOOR PLAN in Figure 2 WARNING TEST YOUR SMOKE ALARM OPERATION AFTER R V OR MOBILE HOME VEHICLE HAS BEEN IN STORAGE BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING USE 2 L...

Страница 5: ...ave inverter These types of inverters are sometimes used to supply power to the structure in off grid installations such as solar or wind derived power sources These power sources produce high peak vo...

Страница 6: ...nnected with other Kidde alarms and accessories as well as specified brands and models of interconnect compatible alarms Connection of Kidde products to a non specified manufac turer s interconnect sy...

Страница 7: ...ring the A C QUICK CONNECT harness as described in the WIRING INSTRUCTIONS attach the trim ring to the electrical box see Figure 5 3 Use a screwdriver to punch out only the pair of holes in the trim r...

Страница 8: ...m A C power TAMPER RESIST LOCKING PIN To make your smoke alarm tamper resistant a locking pin has been provided with your alarm Using this pin will help deter children and others from removing the ala...

Страница 9: ...en the unit senses products of combustion and goes into alarm mode the red LED will flash rapidly one flash per second The rapid flashing LED and temporal alarm will continue until the air is cleared...

Страница 10: ...ing instructions outlined in section 6 of the manual to clean your alarm To check for proper smoke entry into the alarm Kidde recommends using aerosol smoke manufactured by Home Safeguard Industries F...

Страница 11: ...he alarm see Section 3 Figure 6 BATTERY INSTALLATION AND REMOVAL To replace or install the batteries you must first remove the alarm from the trim ring by following the ALARM REMOVAL instruc tions at...

Страница 12: ...BER OPERATION THIS ALARM WILL CHIRP IF ABNORMAL OPERATION OF THE SMOKE SENSING CHAMBER IS DETECT ED THIS CHIRP WILL OCCUR APPROXIMATELY 10 SECONDS AFTER THE RED LED FLASH REPLACE THE ALARM IF THIS CON...

Страница 13: ...ooner than ionization alarms Home fires develop in different ways and are often unpredictable For maximum protection Kidde recommends that both Ionization and Photoelectric alarms be installed A batte...

Страница 14: ...y level of the home and in the kitchen basement and garage Know how to use a fire extinguisher prior to an emergency Current studies have shown smoke alarms may not awaken all sleeping indi viduals an...

Страница 15: ...iple station smoke alarms shall be installed as follows 1 In all sleeping rooms Exception Smoke alarms shall not be required in sleeping rooms in existing one and two family dwelling units 2 Outside o...

Страница 16: ...all rooms and areas of the household as follows A smoke alarm installed in each separate sleeping area in the vicinity of but outside of the bed rooms and heat or smoke detectors in the living rooms d...

Страница 17: ...E ALARM OR UNDER THE TERMS OF THIS LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACE MENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE SAFETY OR ANY OF ITS PAR ENT OR SUBSIDIARY CORPORATI...

Отзывы: