Effective:
October
2020
K-71-101
3
INTEGRATION OF DETECTORS
KS-PS detectors can be mixed in any order with SmartOne
legacy detectors on a Kidde Fire Systems intelligent control unit
running SmartOne protocol.
NOTES:
1.
Detectors are not polarity sensitive. Terminals 3 and 7
(SmartOne legacy detectors) or Terminals 2 and 4 (KS
or DS Series detectors) can be reversed.
2.
Detectors can be installed in any order.
3.
SLC loop is not sensitive to the location of the control unit
(can be left or right end of loop).
4.
Four-wire loops will be wired as shown, bringing loose end
of loop back to the control unit.
COMPATIBLE CONTROL UNITS
*
FACUs running software revision 82.4 are compatibility-tested but
not agency listed with the device(s) in this data sheet.
Fire Alarm
Control Unit
(FACU) Type
Current
Product
Legacy
Product
Single Loop
ARIES
®
-SLX
ARIES
FenwalNET
™
6000
MICRO SLX
PEGAsys
™
*
FenwalNET 2000
*
Multiple Loop
ARIES
®
-MLX
ARIES NET
Link
FenwalNET 8000-ML
MICRO MLX
PEGAsys
*
FenwalNET 2000
*
4
TO
NEXT
DETECTOR
KS-PS or
DS SERIES
DETECTOR
2
7
3
SMARTONE
CPD-7052, PSD-7152
or THD-7252 DETECTOR
TO
CONTROL UNIT
OR
ANOTHER
DETECTOR
(Not Polarity
Sensitive)
Figure 1: Combining Legacy Detectors with KS Series Detectors
(Class B Wiring Style Shown)