Effective: 

October 

2020

K-71-101

3

INTEGRATION OF DETECTORS

KS-PS detectors can be mixed in any order with SmartOne
legacy detectors on a Kidde Fire Systems intelligent control unit
running SmartOne protocol.

NOTES:
1.

Detectors are not polarity sensitive. Terminals 3 and 7
(SmartOne legacy detectors) or Terminals 2 and 4     (KS
or DS Series detectors) can be reversed.

2.

Detectors can be installed in any order.

3.

SLC loop is not sensitive to the location of the control unit
(can be left or right end of loop).

4.

Four-wire loops will be wired as shown, bringing loose end
of loop back to the control unit.

COMPATIBLE CONTROL UNITS

*

FACUs running software revision 82.4 are compatibility-tested but

not agency listed with the device(s) in this data sheet.

Fire Alarm 

Control Unit 

(FACU) Type

Current

Product

Legacy

Product

Single Loop

ARIES

®

-SLX

ARIES
FenwalNET

 

6000

MICRO SLX
PEGAsys

FenwalNET 2000

Multiple Loop

ARIES

®

-MLX

ARIES NET

Link

FenwalNET 8000-ML
MICRO MLX
PEGAsys

FenwalNET 2000

4

TO
NEXT
DETECTOR

KS-PS or

DS SERIES

DETECTOR

2

7

3

SMARTONE

CPD-7052, PSD-7152

or THD-7252 DETECTOR

TO

CONTROL UNIT

OR

ANOTHER

DETECTOR
(Not Polarity

Sensitive)

Figure 1:  Combining  Legacy  Detectors with KS Series Detectors   

    (Class B Wiring Style Shown)

Содержание SmartOne KS-PS

Страница 1: ... readings and compares this information to a preprogrammed setting ADDRESSING KS PS detectors feature electronic addressing No addressing switches are used PROTOCOL This product will operate only on a Kidde Fire Systems fire alarm suppression control unit employing SmartOne communications protocol STATUS LED KS PS detectors use an LED to indicate the detector s condition In normal standby conditio...

Страница 2: ...e 24 VDC nominal Current Normal Operating Alarm 150 µA 220 µA SLC Protocol SmartOne UL cUL smoke sensitivity range 0 5 to 3 50 ft 2 95 to 11 48 m obscuration Open Area Use Only NOTE Smoke sensitivity is selected at the control unit or with the remote configuration software Default values are 2 0 ft Alarm and 1 5 ft Pre Alarm Refer to the Installation Operation and Maintenance Manual or the Configu...

Страница 3: ... wire loops will be wired as shown bringing loose end of loop back to the control unit COMPATIBLE CONTROL UNITS FACUs running software revision 82 4 are compatibility tested but not agency listed with the device s in this data sheet Fire Alarm Control Unit FACU Type Current Product Legacy Product Single Loop ARIES SLX ARIES FenwalNET 6000 MICRO SLX PEGAsys FenwalNET 2000 Multiple Loop ARIES MLX AR...

Страница 4: ... Ashland MA 01721 USA Telephone 508 881 2000 K 71 101 Rev AA 2020 Carrier Kidde Fenwal Chemetron and SmartOne are registered trademarks of Kidde Fenwal Inc or its parents subsidiaries or affiliates SIGA LED Remote Indicator OPTIONAL NOTE Maximum wiring resistance to SIGA LED must not exceed 10 Ohms per wire To next detector From control unit or From previous detector DS SB Standard Base Shown with...

Отзывы: