06-236115-003
1
July 2016
1
GENERAL
To comply with NFPA 2001 (2012 ed.), all control head must be under placement supervision
such that, if an electric actuator is removed, an audible and visual signal will be initiated at the
control panel indicating system impairment. To accomplish this, Kidde is offering a Control
Head Monitor suitable for mounting between the electric control head and the corresponding
discharge valves.
This document provides instructions to install the Control Head Monitor.
For other details, see the Kidde Fire Systems
®
ECS Fire Suppression System with HFC-227ea
Agent: DIOM Rev BA, P/N 06-236115-001.
Содержание ECS
Страница 3: ......
Страница 9: ...THIS PAGE INTENTIONALLY LEFT BLANK October 2014 vi 06 236115 001 ...
Страница 19: ...October 2014 xvi 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 25: ...October 2014 1 6 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 63: ...Component Description October 2014 3 36 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 103: ...Design and Installation October 2014 4 40 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 137: ...Post Discharge Maintenance October 2014 6 18 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...P N 06 236115 001 A 1 October 2014 APPENDIX A MATERIAL SAFETY DATASHEETS ...
Страница 167: ...October 2014 A 2 P N 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 168: ......
Страница 171: ......
Страница 173: ...July 2016 ii 06 236115 003 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 186: ......
Страница 189: ......
Страница 191: ...August 2016 ii 06 237553 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 198: ......
Страница 201: ......
Страница 203: ...May 2016 ii 06 236115 004 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 211: ...May 2016 8 06 236115 004 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 212: ......