Kice Industries, Inc.

012420   /   FLT-M02-0004

Appendix C Continued

Page 3 of 4                                                                                             

I&M No. V_6583_R12   

 

©

ASCO Valve, Inc.

 

50 Hanover Road, Florham Park, New Jersey 07932             www.ascovalve.com  

NOTE:

  Some solenoid constructions have a plugnut/core tube sub-

assembly, bonnet gasket and bonnet in place of the solenoid base sub-

assembly.  To remove bonnet use special wrench adapter supplied in 

ASCO Rebuild Kit.  For wrench adapter only, order ASCO Wrench Kit 

No. K218948.

4. 

The core is now accessible for cleaning or replacement. 

5. 

If the solenoid is part of a valve, refer to basic valve installation and 

maintenance instructions for further disassembly. 

6. 

Reassemble using exploded views for identi

 cation and placement 

of parts.  

ORDERING INFORMATION 

FOR ASCO SOLENOIDS 

When Ordering Solenoids for ASCO Solenoid Operators or 

Valves, order the number stamped on the solenoid. Also 

specify voltage and frequency.  

solenoid with 

1/2" NPT  

wave washer 
valve bonnet 
bonnet gasket 
plugnut/core tube 

sub

-

assembly  

core  

Remove red cap and 

push solenoid down. 

Then pry here to lift 

nameplate/retainer 

and push to remove.  

For special wrench 

adapter order kit 

No. K218948  

spring 

washer  

0.750

-

28UN

-

2A thread 

0.9375

-

26UNS

-

2A thread  

Tapped hole in core 

0.250

-

28UNF

-

2B 

0.38 minimum full thread  

red cap 
nameplate/ 

retainer 

grounding 

wire - green or 

green with 

yellow stripes 

solenoid with 

1/2" NPT 
solenoid base 

sub

-

assembly  

core 

(AC)  

core 

(DC)  

Remove red cap and 

push solenoid down. 

Then pry here to lift 

nameplate/retainer 

and push to remove.  

Side View 

collar to face 

valve body  

spring washer  

3/4" Bonnet Construction                                       15/16" Bonnet Construction 

Alternate Construction 

Figure 1. Series 8016G/H solenoids

red cap 
nameplate/ 

retainer 
spacer 

solenoid  

spring washer  

valve bonnet 

core tube  

Bolted Bonnet Construction 

Figure 2. Series 8016G/H 

solenoids

solenoid with 

1/2" NPT 

1.312 diameter 

mounting hole  

retainer 

spring washer 

valve bonnet  

bonnet gasket  

plugnut/core tube 

sub

-

assembly  

core  

red cap 

nameplate/retainer 

solenoid with 1/2" NPT 

grounding wire

-

 

green or green 

with yellow stripes  

.062 to .093 max. 

thickness of panel 

for mounting  

For special wrench 

adapter order kit 

No. K218948  

3/4" Bonnet Construction  

red cap 

nameplate/retainer  

Remove red cap and 

push solenoid down. 

Then pry here to lift 

nameplate/retainer 

and push to remove.  

spring washer  

0.69 diameter 

mounting hole 
solenoid base 

sub-assembly 

core  

15/16" Bonnet Construction  

Figure 3. Series 8016G/H panel mounted solenoids

Torque Chart  

Part Name

Torque Value in Inch-Pounds

Torque Value in Newton-Meters

solenoid base sub-assembly

175 ± 25

19,8± 2,8

valve bonnet (3/4" bonnet construction)

90 ± 10

10,2 ± 1,1

bonnet screw (3/8" or 1/2" NPT pipe size)

25

2,8

bonnet screw (3/4" NPT pipe size)

40

4,5

Содержание Venturi-Jet

Страница 1: ...dustry Special execution intended for use in potentially explosive atmosphere zone 22 in conformity with category 3 of group II according to the European ATEX Directive 2014 34 EU The equipment has th...

Страница 2: ...ear from the date of shipment Company agrees to repair or replace at its option any parts found to be defective in the opinion of the Company Company is not liable for any costs in connection with the...

Страница 3: ...ation 5 4 Safety Precautions 9 5 Delivery Inspection and Installation Preparation 12 6 Storage 13 7 Installation 13 8 Filter Operation and Start Up Procedure 19 9 Filter Maintenance and Service 26 10...

Страница 4: ...or additional information application assistance or special service please contact us by phone at 316 744 7151 or email at sales kice com We ll need to know the MODEL and SERIAL NUMBER of your Kice Ve...

Страница 5: ...ms disconnect and lockout or lockout tagout as used in this manual means that power to the Kice Venturi Jet filter has been disconnected through the use of a padlockable manual power cutoff or power l...

Страница 6: ...mber For service or assistance ordering parts contact the Customer Service Department or Quick Ship Department Kice Industries Inc 5500 Mill Heights Drive Wichita Kansas 67219 2358 Toll Free 877 289 5...

Страница 7: ...chased items such as speed reducers motors and positive pressure pumps are covered by the manufacturer s warranty If there is a problem with a purchased item check with the local supplier or service r...

Страница 8: ...wing publications provide valuable information on fire and explosion protection and can be helpful to insure your facility is properly equipped NFPA 652 Standard on the Fundamentals of Combustible Dus...

Страница 9: ...ersonal safety When you see this symbol be alert Your personal safety or the safety of others may be affected Follow the instructions in the safety message Safety Decals The Kice Venturi Jet filter de...

Страница 10: ...s all moving parts are completely enclosed and all guards grates and maintenance panels are in place and securely fastened All protective covers guards grates maintenance panels switches and warning d...

Страница 11: ...plete required Kice Venturi Jet filter service Never stand under any kind of hoists or lifting mechanisms whether or not it is loaded or in operation Never stand under or near an Kice Venturi Jet filt...

Страница 12: ...Jet filter is still secured to freight platform Slab Mounted Units A qualified engineer should design the foundation and or footings for the filter The slab should be extended to support accessory eq...

Страница 13: ...ound each hole and mount the filter housing 4 If an airlock valve is required it should be mounted to the hopper discharge flange or sight glass as sembly Additional support may be required 5 Tighten...

Страница 14: ...tank has its own junction box A local electrician must run a conduit from the control box to each junction box on the filter Wiring from the controller to the junction box terminals should be 18 gaug...

Страница 15: ...form make sure the tabs on both sides of the cleaning platform are on the outside of the door frame Check to make sure the cleaning platform is level and secure The platform should not rest against or...

Страница 16: ...stem NOTICE Kice Industries Inc will always supply internal safety grating in the bottom of the filter housing if it is to be mounted onto a storage bin to prevent personnel bags and cages from droppi...

Страница 17: ...igure 7 Installation Continued Figure 7 2 Check the filter bag for proper length The filter bag should be only 2 longer than the bag retainer cage 3 Tuck the overextended portion of the filter media i...

Страница 18: ...the assembly from slipping off see Figure 11 7 Tighten the clamp with either a screwdriver a nut runner with a 5 16 socket or a ratchet with an extension which will help facilitate the installation It...

Страница 19: ...r media to be dislodged and fall into the hopper After an adjustable amount of time the controller cycles to the next Kice Venturi Jet blast valve in sequence and activates its solenoid which releases...

Страница 20: ...ntroller will activate the outputs sequentially whenever the pressure switch contacts are closed When the pressure switch contacts open the output sequencing stops Reclosing of the contacts will cause...

Страница 21: ...ration Start Up Procedure Continued The DCT510ADC operates on 10 to 35 VDC The DCT500ADC Low Cost Timer Controller is designed for continuous cleaning methods or on demand pulse jet cleaning systems D...

Страница 22: ...from 10 to 600 Milliseconds Operating Voltage 120 10 VAC 50 60 Hz O Time Adjustable from 1 to 180 Seconds DCT1022DC Adjustable from 1 to 225 Seconds Optional Voltage 220 10 VAC 50 60 Hz Output Protec...

Страница 23: ...lied continuously to terminals L1 and L2 the number 1 output on time will activate followed by an independently timed off period Each time sequence is infinitely adjustable within the stated time rang...

Страница 24: ...5 11 20 DNC T2032 A10 1 5 30 32 14 x 12 x 6 17 32 1994 to 2008 Figure XX Specifications Time Delay Input On Time Adjustable from 50 to 500 Milliseconds Operating Voltage 120 10 VAC 50 60 Hz O Time Ad...

Страница 25: ...a short run in time for the electronics 5 Set the controller off time adjustment to a longer time span by rotating the dial clockwise until you cannot turn the dial any further With the off time adjus...

Страница 26: ...2 Excessive leakage Disassemble valves and clean all parts Replace parts that are worn or damaged with a complete Spare Parts Kit 96 875 3 Failure to Open or Close a If the blast valve stays open the...

Страница 27: ...lenoid enclosure NOTICE Reference ASCO Valves installation and maintenance instructions in Appendix B Solenoid Description The Kice pilot valve is operated by an ASCO Red Hat II epoxy encapsulated sol...

Страница 28: ...the dust may buildup to the point that the filter media needs to be removed for cleaning This condition may be corrected by running the cleaning cycle without the dusty air flowing through the filter...

Страница 29: ...olenoid valve 3 Check the compressed air line manually operated maintenance valve 4 Check the venturi jet blast valves for leaks 5 Check to see if any of the venturi jet blast valves are stuck open an...

Страница 30: ...e 4 DO NOT mount the control in a high transient voltage area without an isolation transformer 5 DO NOT leave the control box door open 6 DO NOT allow a local repair shop to repair the controller For...

Страница 31: ...SCO Valve Inc 50 Hanover Road Florham Park New Jersey 07932 www ascovalve com E21903 12 11 Page 1 of 2 All Rights Reserved I M No V 5162 R6 I M No V 5162 R6 31 Kice Industries Inc 012420 FLT M02 0004...

Страница 32: ...LT M02 0004 Appendix A Continued Page 2 of 2 Page 2 of 2 ASCO Valve Inc 50 Hanover Road Florham Park New Jersey 07932 www ascovalve com ASCO Valve Inc 50 Hanover Road Florham Park New Jersey 07932 www...

Страница 33: ...Inlet port will either be marked 1 or IN Outlet port will be marked 2 or OUT see Figure 1 Future Service Considerations Provision should be made for performing seat leakage external leakage and operat...

Страница 34: ...are possible The actual frequency of exercise necessary will depend on speci c operating conditions A successful operating history is the best indication of a proper interval between exercise cycles D...

Страница 35: ...que Chart Torque value Inch Pounds 175 25 Torque value Newton Meters Suf x P 19 8 2 8 solenoid base sub assembly core assembly with core spring and rider ring core guide solenoid base gasket valve bod...

Страница 36: ...ontal position retainer ring 2 Reinstall retainer ring on body and lock retainer into the stem groove for proper engagement 3 Position core assembly with core spring into base of valve body 4 Replace...

Страница 37: ...cy WARNING Electrical hazard from the accessibility of live parts To prevent the possibility of death serious injury or property damage install the open frame solenoid in an enclosure FOR BLACK ENCLOS...

Страница 38: ...enoid base sub assembly through 0 69 diameter mounting hole in customer panel 2 Position spring washer on opposite side of panel over solenoid base sub assembly then replace Solenoid Temperature Stand...

Страница 39: ...hread red cap nameplate retainer grounding wire green or green with yellow stripes solenoid with 1 2 NPT solenoid base sub assembly core AC core DC Remove red cap and push solenoid down Then pry here...

Страница 40: ...DIN Terminals terminal block screw Indicates parts supplied in Termination Module Kit No K256104 5 32 hex key wrench socket head screw Figure 4 Open frame solenoids screw terminal block see note junc...

Страница 41: ...cabinet can only be opened with a key The following has been prepared in reference to EU directives 2014 34 EC so that Kice Filters applied in locations under this directive may meet the requirements...

Страница 42: ...filters If heavy machine components e g heavy parts of the housing must be dismantled to carry out service and maintenance activities suitable lifting equipment must be used When installing parts ins...

Страница 43: ...8 Socket head Socket head cap screw cap screw Bolt Thread Dia Size 1 4 20 8 4 11 12 16 11 15 5 16 18 17 24 25 33 23 31 3 8 16 31 42 44 59 41 55 7 16 14 49 67 70 95 65 59 1 2 13 74 100 110 140 100 140...

Страница 44: ...44 Kice Industries Inc 012420 FLT M02 0004 2016 Kice Industries Inc 5500 N Mill Heights Dr Wichita KS 67219 2358 P 316 744 7151 F 316 744 7355 sales kice com kice com...

Отзывы: