BFC Airflow Setpoint
Step 1:
Determine if BFC will be controlled using local control, BAS analog voltage signal, or BACnet. The control mode can
be confirmed by observing the cycling status readout on the LCD.
NOTE:
The control hierarchy is BACnet > BAS > Local. The control mode is based on the highest level of control provided.
Step 2:
For Local or BACnet control, determine the setpoint from the appropriate airflow formula for your model in the tables
below.
If BFC is being controlled by BAS analog voltage signal, refer to "ECMSC Airflow Setpoint" section for proper input voltage
(Note this will be 2X the VDC value shown in the tables).
Set-point (ECM%) ranges from 0% - 100%
To calculate FPM from a CFM value use the equation for the respective unit style and size from the following table.
RSR
BTR
2x2
CFM/2.30
CFM/3.31
2x3
CFM/3.82
CFM/5.13
2x4
CFM/5.33
CFM/6.95
Supply - Constant Flow - Forward Curve
Velocity
24x24
24x36
24x48
FPM
BTR - FC
RSR - FC
BTR - FC
RSR - FC
BTR - FC
RSR - FC
45-140
ECM% =
(CFM ÷ 3.40) - 42
ECM% =
(CFM ÷ 2.35) - 43
ECM% =
(CFM ÷ 5.08) - 44
ECM% =
(CFM ÷ 4.45) - 32
ECM% =
(CFM ÷ 6.93) - 42
ECM% =
(CFM ÷ 5.50) - 41
Supply - Constant Torque - Forward Curve
Velocity
24x24
24x36
24x48
FPM
BTR - FC
RSR - FC
BTR - FC
RSR - FC
BTR - FC
RSR - FC
45-95
ECM% =
(CFM ÷ 10.82) - 12
ECM% =
(CFM ÷ 8.86) - 10
ECM% =
(CFM ÷ 11.27) - 13
ECM% =
(CFM ÷ 9.56) - 14
ECM% =
(CFM ÷ 11.76) - 17
ECM% =
(CFM ÷ 13.06) - 5
95-140
ECM% =
(CFM ÷ 7.25) - 26
ECM% =
(CFM ÷ 6.09) - 21
ECM% =
(CFM ÷ 6.90) - 39
ECM% =
(CFM ÷ 5.85) - 42
ECM% =
(CFM ÷ 7.42) - 47
ECM% =
(CFM ÷ 6.65) - 41
Supply - Constant Torque - Backward Curve
Velocity
24x36
24x48
FPM
BTR - BC
RSR - BC
BTR - BC
RSR - BC
45-140
ECM% = (CFM ÷ 15.75) - 13
ECM% = (CFM ÷ 14.53) - 6
ECM% = (CFM ÷ 16.07) - 17
ECM% = (CFM ÷ 17.99) - 6
Reverse/Exhaust Flow - Constant Flow - Forward Curve
Velocity
24x24
24x48
FPM
RSR - FC
RSR - FC
45-140
ECM% = (CFM ÷ 2.38) - 39
ECM% = (CFM ÷ 5.53) - 40
Reverse/Exhaust Flow - Constant Torque - Forward Curve
Velocity
24x24
24x48
FPM
RSR - FC
RSR - FC
45-95
ECM% = (CFM
÷
6.90) - 16
ECM% = (CFM
÷
10.78) - 15
95-140
ECM% = (CFM
÷
6.90) - 16
ECM% = (CFM
÷
6.86) - 42
Supply, 24 x 48 in., RSR, FC Wheel, Constant Torque @ 550cfm
FPM = CFM/5.33 = 550/5.33
FPM = 103
ECM% = (CFM/6.65)-41 = (550/6.65)-41
ECM% = 42%
NOTE:
The calculated ECM% value is intended as a starting point; actual ECM% value may differ slightly depending on field
variables.