3 - PRELIMINARY CHECKS
2.4 - List of cables required
The cables required for connection of the various devices in a stan
-
dard system are listed in the cables list table.
ELECTRIC CABLE TECHNICAL SPECIFICATIONS:
Connection
cable
maximum allowable limit
Control unit power supply line
1 x cable 3 x 1,5 mm
2
20 m *
Flashing light
Antenna
1 x cable 4 x 0,5 mm
2
**
1 x cable type RG58
20 m
20 m (advised < 5 m)
Transmitter photocells
1 x cable 2 x 0,5 mm
2
20 m
Receiver photocells
1 x cable 4 x 0,5 mm
2
20 m
Sensitive edge
1 x cable 2 x 0,5 mm
2
20 m
Key-switch
1 x cable 4 x 0,5 mm
2
20 m
Before installing the product, perform the following checks and in-
spections:
check that the gate or door is suitable for automation;
the weight and size of the gate or door must be within the operating
limits specified for the automation system in which the product is
installed;
check that the gate or door has firm, effective mechanical safety
stops;
make sure that the product fixing zone is not subject to flooding;
high acidity or salinity or nearby heat sources might cause the pro-
duct to malfunction;
in case of extreme weather conditions (e.g. snow, ice, wide tempe-
rature variations or high temperatures), friction may increase, cau-
sing a corresponding rise in the force needed to operate the system;
TECHNICAL SPECIFICATIONS:
Power supply
230 Vac (+10% - 15%) 50-60 Hz
Max motor load
600 W
Output for accessories power
24 Vac 1,5 W MAX
Flashing light output
230 Vac 40 W
Pause time
da 4 a 120 sec.
Work time
da 1 a 180 sec.
Operating temperature
-20 + 55 °C
Receiver frequency
433.92 MHz
Available reception
fix code/rolling code
Max. number of transmitters storage
1000 TX
Impedance of antenna
50 Ω
Capacity
50-150 m in unlimited space
the starting torque may therefore exceed that required in normal
conditions;
check that when operated by hand the gate or door moves smoothly
without any areas of greater friction or derailment risk;
check that the gate or door is well balanced and will therefore re-
main stationery when released in any position;
check that the electricity supply line to which the product is to be
connected is suitably earthed and protected by an overload and dif-
ferential safety breaker device;
the system power supply line must include a circuit breaker device
with a contact gap allowing complete disconnection in the condi-
tions specified by class III overvoltage;
ensure that all the material used for installation complies with the
relevant regulatory standards.
The cables used must be suitable for the type of installation; for
example, an H03VV-F type cable is recommended for indoor appli-
cations, while H07RN-F is suitable for outdoor applications.
* If the power cable is longer than 30 m, a cable with a larger cross-section is required (3x2.5 mm
2
) and safety earthing is necessary in the
vicinity of the automation.
** Two cables of 2 x 0.5 mm
2
can be used as an alternative