23
En
PARAMETERS
DESCRIPTION
DEFAULT
MIn
MAX
UNIT
TYPE
1
Deceleration lenght
Determines how far in advance reduced speed is imposed to
the switch's stop.
50
0
200
Cm
(step 10)
2
Ramp acceleration and deceleration time.
The lower the value, the shorter and sharper is the ramp.
30
10
30
3
Impact force on obstacle: allows faster reaction time on the
obstacle (e.g. impact in the absence of rubber edge), lower
value = faster reaction time
90
0
100
4
Further acceleration at start. useful to speed up the opening
of the barrier.
1
0
1
bA
5
Obstacle/edge reverse time (0 = disabled)
3
0
20
s
sL
6
Pedestrian opening lenght
Determines the partial opening of the installation from the
CLOsED position.
50
0
990
Cm
(step 10)
sL
7
Pedestrian opening automatic auto-reclosing time
20
0
600
s
(step 10)
(step 10)
(step 10)
sL
8
Photocell F2 confi guration
0.
Enabled for both opening and closing OP/CL
1.
Enabled only for opening OP
0
0
1
9
Enables opening with F1 obscured
1
0
1
10
Man Present confi guration (only for open/close inputs)
0.
0. Disabled
1.
1. Man Present
0
0
1
11
Clearance. Allows to stop before the fully open position: it is
useful to avoid mechanical stress during opening.
0
0
100
bA
12
Pre-fl ashing time
0
0
10
s
13
Courtesy light timer
0
0
900
s
(step 10)
14
Courtesy light confi guration
1. On if courtesy light timer TCY is not expired
2. On if the gate is not TCY time
2. On if the gate is not TCY time
2. On if the gate is not TCY time
1
1
2
15
Courtesy litht level at the end of the manouvre (0 = light is off,
other values light will stay on all the time at the desired level)
0
0
100
16
Open gate light confi guration
0.
On/OFF
1.
Modulated by the position of the gate
2.
Magnetic electric lock function ( interface with a
24V external relay). To activate this function it is
necessary to activate also pre-fl ashing for 1 sec.
(tPr = 1)
0
0
2
17
Cycles before Maintenance (0 = disabled). When level set is
reached the next cycles will be done with a fast fl ashing to
advise the user
0
0
100
1000
cycles
18
Enables the constant fl ashing of the request for maintenance
(function performed only when the gate is closed)
Under battery back-up fl ashing will not be performed
0
0
1
19
number of encoder impulses per motor revolution
4
1
16
sL
20
sets default values and type of control
0.
sliding
1.
barrier
2.
sliding 400 Kg (nEP=1*) - LsI blocked at 50
sliding 400 Kg (nEP=1*) - LsI blocked at 50
sliding 400 Kg (nEP=1*) - LsI blocked at 50
0
0
1
To set the default values: 1) Enter the advanced programming 2) Select the "dEf" parameter 3) Activate the edit mode (displays "0" fl ashing)
4) Accept the change (press "MEnu" button for 2 seconds). At this point you should see a countdown d80,d79.....d02,d01
The
ADVAnCED MEnu allows you to further customize the instal-
lation by changing some parameters not accessible from the basic
menu
To access the ADVANCED menu, hold down the MENU button for 5
seconds. To change the parameters of the ADVANCED MENU pro-
6 - INsIGHTs - ADVANCED MENU
ceed as indicated for the bAsIC MEnu
In the last column are indicated the parameters used only for a
specifi c type of automation: SL sliding motor, BA barrier, BL over-
head, sE sectional.
* nEP value depends on motor encoder typology.
* Values for 400 Kg sliding motors.