3 - prElIMINAry CHECKs
2.4 - list of cables needed
Typical installation cables required for connection of various devices
are shown in cables list table.
before installing the product, perform the following checks and in-
spections:
check that the gate or door is suitable for automation;
the weight and size of the gate or door must be within the operating
limits specifi ed for the automation system in which the product is
installed;
check that the gate or door has fi rm, effective mechanical safety
stops;
make sure that the product fi xing zone is not subject to fl ooding;
high acidity or salinity or nearby heat sources might cause the pro-
duct to malfunction;
in case of extreme weather conditions (e.g. snow, ice, wide tempe-
rature variations or high temperatures), friction may increase, cau-
sing a corresponding rise in the force needed to operate the system;
the starting torque may therefore exceed that required in normal
conditions;
check that when operated by hand the gate or door moves smoothly
without any areas of greater friction or derailment risk;
check that the gate or door is well balanced and will therefore re-
main stationery when released in any position;
check that the electricity supply line to which the product is to be
connected is suitably earthed and protected by an overload and dif-
ferential safety breaker device;
the system power supply line must include a circuit breaker device
with a contact gap allowing complete disconnection in the condi-
tions specifi ed by class III overvoltage;
ensure that all the material used for installation complies with the
relevant regulatory standards.
The cables used must be suitable for the installation; for example,
we recommend a H03VV-F type cable for indoor installation and
H07RN-F for outdoor.
2.4 - list of cables needed
- Power supply protected against short circuits within the unit, on
motor and connected accessories.
- Power adjustment with chopping of the current.
- Detection of obstacles by monitoring the encoder from the motor.
- Automatic learning of the working time.
- Disabling of safety inputs via dip switches: no need to bridge the
terminals related to the safety not installed, by simply disabling the
function with the dip switch.
- Ability to operate with an optional battery without power supply.
- Low voltage output used for a status indicator light or a 24V fl ash-
ing light.
- Energy savings function.
TECHNICAL SPECIFICATIONS:
Power supply (L-n)
230Vac (+10% - 15%) 50/60 Hz
nominal power
210W
Auxiliary power supply
stabilized 24 Vdc (max 200 mA)
Flashing light output
24Vdc 25W
Courtesy light output
24Vdc 25W
Gate open indicator output
24Vdc 4W
Antenna input
50Ω cable type RG58
Operating temperature
-20°C + 55°C
Main system fuses
10AT
Accessory fuses
2,5AT
Power supply line fuses
2AT
use in particularly acid, saline or explosive atmospheres
nO
ELECTRIC CABLE TECHNICAL SPECIFICATIONS:
Connection
cable
maximum allowable limit
Power supply line
1 x cable 3 x 1,5 mm
2
20 m *
Flashing light with antenna
1 x cable 2 x 0,5 mm
2
1 x cable type RG58
20 m
20 m (advised < 5 m)
Transmitter photocells
1 x cable 2 x 0,5 mm
2
20 m
Receiver photocells
1 x cable 4 x 0,5 mm
2
20 m
sensitive edge
1 x cable 2 x 0,5 mm
2
20 m
Key-switch
1 x cable 4 x 0,5 mm
2
20 m
* If the power cable is longer than 30 m, a cable with a larger cross-section is required (3x2.5 mm
2
) and safety earthing is necessary in the
vicinity of the automation.