2-4 Measurement specification
Loop impedance
Prospective Short-circuit Current
(*1): If the impedance between L-N is 20
Ω
or more, "no" is
displayed on the LCD and no measurement can be made. In this
case, disables ATT function and make measurement.
6
Measuring
Nominal test current at
Intrinsic
Range
range
0
Ω
external loop:
accuracy
Magnitude/Duration
20
Ω
0.00-19.99
Ω
25A/10ms
200
Ω
0.0-199.9
Ω
2.3A/20ms
±(3%rdg+4dgt)
2000
Ω
0-1999
Ω
15mA/360ms
20
Ω
0.00-19.99
Ω
(ATT)
(*1)L-N<20
Ω
P-N:25A/30ms
±(3%rdg+6dgt)
200
Ω
0.0-199.9
Ω
N-E:11mA/approx. 2s
(ATT)
(*1)L-N<20
Ω
Measuring
Nominal test current at
Intrinsic
Range
range
0
Ω
external loop:
accuracy
Magnitude/Duration
200A
0.0-199.9A
2.3A/20ms
2000A
0-1999A
25A/10ms
20kA
0.00-1.99kA
25A/10ms
200A
0.0-199.9A
(ATT)
(*1)L-N<20
Ω
2000A
0.0-1999A
P-N:25A/30ms
(ATT)
(*1)L-N<20
Ω
N-E:11mA/approx. 2s
20kA
0.00-1.99kA
(ATT)
(*1)L-N<20
Ω
PSC accuracy is
derived from the
loop impedance
accuracy
PSC(ATT)
accuracy is
derived from the
loop (ATT)
impedance
accuracy