The KT45 incorporates Anti Trip Technology (ATT) which
electronically by-passes most RCDs at Distribution
Boards. This saves time and money by not having to take
the RCD out of circuit during testing and is a safer
procedure to follow.
With the ATT function, a test current of 15mA or less is
applied between line - earth. It enables LOOP
measurement without tripping most RCDs.
If there is doubt as to whether this tester will by-pass a
particular RCD, contact Kewtech with details of
manufacturer, model no., rating and sensitivity.
Please read this instruction manual carefully before using
this instrument.