4. Operating instructions
4.1 Initial Checks: to be carried out before any testing;
4.1.1 Preparation
Always inspect your test instrument and lead accessories for
abnormality or damage-If abnormal conditions exist DO
NOT PROCEED WITH TESTING. Have the instrument
checked by Kewtech.
(1) Operate the Power button and turn on the instrument.
Turn the Function switch and set it to any range at the
LOOP or PSC.
(2) Insert the Test Lead into the instrument.(Fig.3)
(3) Pressing the Noise override switch disables ATT mode.
Then the "ATT" mark on the LCD will disappear.
▲
ATT mode enables a measurement without tripping the
RCDs with the rated residual current of 30mA or more.
▲
Measurement in ATT mode requires longer time than that
is required for the other measurements (approx. 10 sec).
When measuring a circuit with a large electrical noise, the
'NOISE' mark is displayed on the LCD and the
measurement time will be extended to 20 sec. When the
noise is so great as to influence the test result the 'NOISE'
symbol will flash and --- will appear in the screen. If the
'NOISE' mark is displayed on the LCD, it is recommended
to disable the ATT mode and take a measurement (RCDs
may trip).
▲
If the impedance of 20
Ω
or more exists between L-N, "no"
is displayed on the LCD and no measurement can be made.
In this case, disable the ATT function and make
measurement. When a large contact voltage exists in the