2.6 MOUNTING THE BOILER
2.7 VENTILATION
•
Due care should be taken when lifting the
boilers, with respect to their weights, see
Table 2 on Page 6. Also refer to Section 1.4
Safe Handling.
1. Lift the boiler onto the wall mounting plate as
shown. Note: It is not necessary to hold the
boiler at an angle to engage the wall mounting
plate.
2. Using the remaining coach screws, secure
the bottom of the boiler to the wall through the
attached brackets.
IMPORTANT NOTE It is essential that these bolts
be fitted prior to making up the flow and return
connections to the boiler to prevent the boiler
becoming detached .
Keston Heat 45/55 (multiple boiler applications)
Detail reference should be made to BS. 6644 for inputs
between 70kW and 1.8MW (net). In IE refer to the current
edition of I.S.820. The following notes are for general
guidance only:
If ventilation is to be provided by means of permanent
high and low vents communicating direct with outside air,
then reference can be made to the sizes below. For other
ventilation options refer to BS. 6644. In IE refer to the
current edition of I.S.820.
Keston ventilation requirements when installed in a compartment up to 70kW (BS5440)
To a room or internal space
To outside Air
Model
45 & 45P
55 & 55P
45 & 45P
55 & 55P
Min Free Area (cm
2
)
432
527
216
263
If installing in a room or internal space then no purpose provided ventilation is required. When installing in a compartment,
the table below details the ventilation requirements in line with BS5440.
17
Installation & Servicing
SECTION 2 - INSTALLATION
INST
ALLA
TION