45
Models:
KESSUPS 91RT
KESSUPS 91RT (2 AC lines)
Available powers (kVA / kw) (**)
0.7 / 0.63
1 / 0.9
1.5 / 1.35
2 / 1.8
3 / 2.7
4 / 3.6
5 / 4.5
6 / 5.4
8 / 7.2
10 / 9
Technology
on-line double conversion, PFC, double DC bus
Rectifier
Generals
iEC inlet connectors
iEC connector 10 A
iEC connector16 A
-
input terminals (Phase + n PE)
-
3
bypass terminals (Phase + n PE)
-
3
iEC outlets connectors
8 iEC 10A (4 x lS1 + 4 x lS2) + 1 iEC 16 A (3 kVA UPS only)
4 iEC 10A + 2 iEC 16 A
8 iEC 16 A
output terminals
-
3 (Phase, neutral and PE)
Communication ports
2 (RS232 -Db9- and USb, mutually exclusive)
Monitoring software
winPower (free download)
option cards (to be inserted into the slot)
Relays interface, SnMP, remote internet or intranet management
noise level at 1 m.
< 45 db
< 50 db
< 55 db
operating temperature
0.. +40 ºC
0.. +45 ºC
Storage temperature
–15.. +50 ºC
Storage temperature without batteries
– 20.. +70 ºC
operating altitude
< 1000 m a.s.l. (for high altitude correct it according to table 14)
Relative humidity
0-95 % non-condensing
Protection degree
iP20
Dimensions -Depth x width x Height- (mm):
UPS
436 x 438 x 86.5 (2U)
608 x 438 x
86.5 (2U)
560 x 438 x 132 (3u)
560 x 438 x 215.5 (5u)
Terminals
-
70 x 194 x 118
80 x 416 x 108
Total dimensions UPS + terminals
-
630 x 438 x 132 (3u)
640 x 438 x 215.5 (5u)
battery
436 x 438 x 86.5 (2U)
608 x 438 x
86.5 (2U)
-
-
UPS weight (kg)
14
15
19
19.5
29
45
47
47
82
83
battery module weight (kg)
23
28
41
-
-
Safety
En-iEC 62040-1; En-iEC 60950-1
Electromagnetic compatibility (EMC)
En-iEC 62040-2
Marking
CE
Quality system
iSo 9001 and iSo 140001
(**)
As frequency converter mode, the supplied power is a
70 % of the nominal.
Tab. 11.
General technical specifications.
Altitude (m.)
1000
1500
2000 2500 3000 3500 4000 4500 5000
Power
100%
95%
90%
85%
80%
75%
70%
65%
60%
Tab. 12.
Correction of power rate as regards to operating altitude.