ALARM CIRCUIT.  

The HSF includes an isolated internal relay offering normally closed and normally open contacts refer-

enced to an isolated common. These contacts may be used to configure “close on failure” or “open on failure” alarm circuits.

(Refer to the Series RA 19-(X)B Manual for alarm configurations for multiple HSF power supplies.)

KEYING. 

Keying of the HSF is established at the factory. The output voltage determines which keyway is open. When the

corresponding rack adapter key (pin) is installed by the user, only a power supply of the correct voltage can be inserted in the

rack adapter slot.

FIGURE 1.  HSF 150 WATT POWER SUPPLIES (6) INSTALLED IN RA 19-6B RACK ADAPTER

III — SPECIFICATIONS

The following specifications apply to all HSF 150 Watt Series models (also refer to Table 1). Other models are also available;

consult your Kepco representative for their specifications.

INPUT: 

Voltage: 120V a-c/240V a-c nominal; Range 95-264V a-c; 125-370V d-c. (polarity insensitive)

Frequency: Nominal 50-60 Hz; Range 47-440Hz (at 440Hz leakage current exceeds UL/VDE safety spec.limit).

Current (nominal output at rated load): @120V a-c rms: 3.0A a-c typ., 3.5A a-c max; 

@240V a-c rms: 1.5A a-c typ., 2.0A a-c max.

Initial Turn-on Surge: (one-half of first input cycle): @120V a-c rms, 25A max; @240V a-c rms, 50A max. When the a-c 

input power is removed, the inrush current limit circuit requires 30 seconds recovery time before the a-c input power 

is reconnected.

Brownout Voltage: 85V a-c, 110V d-c.

Switching Frequency: 120KHz typical, nominal load.

STABILIZATION: 

Source Effect: Range 95-132V a-c or 190-264V a-c, 1.0% typ.; 2.0% max.

Load Effect: Range 10%-100% load, 1.0% typ.; 2.0% max.

Temperature Effect: Range 0

o

 to 40

o

C, 1.0% typ.; 2.0% max.

Combined Effect: 2.0% typ.; 4.0% max. (includes source, load, and temperature effects).

Time Effect: 0.1% typ.; 0.5% max. (1/2 hr-8 hr at 25

o

C).

RECOVERY CHARACTERISTICS:  

A step load change from 50% to 100% produces less than +4% output excursion.

Recovery occurs to 1% of the original setting in <1 ms (load change t

or t

f

 equal to or greater than 50

µ

sec).

START-UP TIME:  

200 ms. maximum. 

HOLDUP TIME:  

20 ms. typ. (120V a-c), 15 ms. min. (100V a-c).

DIELECTRIC STRENGTH: 

 

Between input and output: 2KV a-c for one minute.

Between input and output with Y-capacitor removed: 3KV a-c for one minute.

Between input and case (ground): 2KV a-c for one minute.

INSULATION RESISTANCE: 

 Between input and ground, output and ground, input and output;

100 Megohms min. (500V d-c).

LEAKAGE CURRENT  

UL method, 120V a-c: 0.5 mA maximum.

VDE method, 240V a-c: 0.75 mA maximum.

Содержание HSF 12-12

Страница 1: ... OFF switch must be set to OFF before removing unit from rack adapter The front panel MASTER ON LED lights when 1 the unit operates independently or 2 the unit is used in parallel redundant configurations while a the output is less than 10 of nominal or b the output is within 10 to 100 of nominal and the unit is functioning as a master In parallel redundant configurations the module with the highe...

Страница 2: ...it Current nominal output at rated load 120V a c rms 3 0A a c typ 3 5A a c max 240V a c rms 1 5A a c typ 2 0A a c max Initial Turn on Surge one half of first input cycle 120V a c rms 25A max 240V a c rms 50A max When the a c input power is removed the inrush current limit circuit requires 30 seconds recovery time before the a c input power is reconnected Brownout Voltage 85V a c 110V d c Switching...

Страница 3: ...t to the load goes below 10 for each unit in current share mode all MASTER ON lights may go on see load effect specifications this indicates that forced cur rent share is no longer working units are simply in current share mode If forced current sharing at less than 10 nominal current per supply is needed contact Kepco application engineering Remote sensing is recommended For master slave operatio...

Страница 4: ...z 10 mm amplitude 10 55 Hz 2g acceleration SHOCK non operating one half sinusoidal pulse three shocks to each axis Acceleration 20g Duration 11ms 5ms OPERATING TEMPERATURE See Figure 4 STORAGE TEMPERATURE 40o C to 75o C OPERATING AND STORAGE RELATIVE HUMIDITY up to 95 wet bulb temp 35o C non condensing FUSE Quick acting 6 3A 250V 5 2 x 20mm San O P N EQ6 3A Kepco P N 541 0113 DIMENSIONS See Figure...

Отзывы: