USER MANUAL
5.2.3
Use of sensors
CAUTION!
Do not supply the voltage of more than 42V to the sensors inputs.
The DKI-02 sensor
This sensor facilitates operation in congested areas. The pins shall
be arranged or rearranged over the axis of the utility at the distance
from each other not exceeding the depth of line.
The “A-frame” sensor
WARNING!
For correct readings of depth and direction during fault finding
always use the A-frame of a new type supplied with insulating
insert, as shown in Fig. Old A-frame may cause false readings of
depth.
As compared with the DKI-
02 sencor, the “A-frame” provides more
accurate readings from measurement to measurement, since the
fixed distance between the pins
eliminates signal fluctation error caused by different distances.
Measurements with this sensor, however, require the pins to be
embedded into the soil, that may be unconvenient in some cases.
Keep the insulator surface of the A-frame clean. Soiling may cause
signal drop or loss of sensitivity.
The DKI-E sensor
This sensor accelerates tracing of single expanded utilities.
The sensor operability does not depend on the type of soil or paving.
The sensor, however, has lower sensitivity, particularly at low
frequencies. Each operator holds a contact electrode of the sensor
during operation. If tracing is performed close to the fault, the
distance between the operators shall be reduced to clarify the
position of cable failure.
The DKI-P sensor
This sensor is an electric antenna fixed to the magnetic antenna
module. The operation of this sensor is similar to the operation of the
DKI-E sensor, but it requires only one operator. This sensor,
however, has lower sensitivity. Strong wind or contact with grass may
cause instable readings.