Unit selection

Unit°C
Unit °F

Operating Scale Minimum Value

(Scale Low Point, Scale High Point)Unit

Used for Proportional band calculation and display blink.

Display offset for process value (Scale -10%, Scale

+10%)Unit

This parameter value is added to the process value.

Unit is Voltage.Active if

Voltage / Current input is selected

Z

No unit.Active if

oltage / current input is selected

Z

V

Coefficient value (1.000, 9.999)

Process value is multiplied with this value.

Active if

Voltage / Current input is selected.

Z

mV

Z

50

Po00 = 0

Po01

Po02

Po03

Po04

Po05

Po16

Po06

Po15

Po07

Po08

Po09

Po10

3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125

3.125 6.25 9.375

12.5 15.625 18.75 21.825

25

28.125 31.25 34.375 37.5 40.625 43.75 46.875

Po14

Po13

Po12

Po11

Process

Set value

0-50 mV

range are divided into 16 egual parts. Every “Poxx” SET value is defined

50 / 16 = 3.125 mV

range.

Z

Z

Filter Time (0.0, 900.0)Second

Defines filter time for display value.

Cold Junction Compensation

This parameter is active if process input is selected TC input.

Cold junction compensation is active.
Cold junction compensation is not active.

Operating Scale Maximum Value

(Scale Low Point, Scale High Point)Unit

Used for Proportional band calculation and display blink.

Scale:

The difference, between high point and low point of the process

input type. Example: If tCSL = 2 (low point is -200, high point is 900),

then scale is 1100. If input type is Voltage/Current, then the scale is

difference between tPoH and tPoLparameters.

PID

 ConF:

 

PID Configuration Parameters

PROPORTIONAL BAND (0.0, 999.9)%

If              = 1000 °C,              = 0 °C and             = 50.0

then Proportional Band = (            -            ) *             / 100.0

Proportional Band = (1000-0)*50.0/100.0 = 500 °C

INTEGRAL TIME (0, 3600)Second

Can be changed by the user. After complated the tunning

correctly, integral time value changes automatically. If it is 0,

integral control is deactivated.

DERIVATIVE TIME (0.0, 999.9)Second

Can be changed by the user. After complated the tunning

correctly, integral time value changes automatically. If it is 0,

derivative control is deactivated.

CONTROL PERIOD TIME (1, 150)

Process output period time

Second

MINIMUM CONTROL OUTPUT (0.0,          )%

Even as a result of the PID calculation device calculates the

%output value less than this parameter, heating or cooling

output is active minimum for OLLparameter.

MAXIMUM CONTROL OUTPUT (           , 100.0)%

Even as a result of the PID calculation device calculates the %

output value greater than this parameter, heating or cooling

output is active maximum for OULparameter.

HEATING MINIMUM CONTROL OUTPUT TIME

(0.0,           )sec

Heating output can not be active less than this parameter.

Even if this parameter is 0, this parameter is accepted

50 msecs for security.

COOLING PROPORTIONAL BAND COEFFICIENT

(0.0, 100.0)

If heating and cooling PID is used in a system, tune operation is

performed by heating output.Cooling proportional parameter is

calculated with heating proportional band value and coefficient

(P-

CL = P-Ht * CCoE / 100.0)

COOLING PROPORTIONAL BAND ( 000.0% , 999.9% )

If

Proportional Band

Proportional Band

= 1000 °C,

= 0 °C and             = 50.0 ise

= (

-

) *

/ 100.0

= (1000-0)*50.0/100.0 = 500 °C

COOLING

 

INTEGRAL

 

TIME (0000 sec, 3600 secs)

It can be changed by the user. When tune operation finishes,

it can be changed by the device. If it is 0, integral control

part does not perform.

COOLING

 

DERIVATIVE TIME (000.0 sec, 999.9 secs)

It can be changed by the user. When tune operation finishes, it can be

 

changed by the device. If it is 0, derivative control part does not perform.

 

When tune operation finishes if this parameter is 0, it can not

be changed because derivative control part does not perform.

COOLING OUTPUT PERIOD TIME (1 sec, 150 secs)

It is control period of cooling output.

COOLING MINIMUM CONTROL OUTPUT

( 0.0,          )%

           ,100.0)%

It is % of cooling minimum output. If heating and cooling PID

 

control functions operate together, this parameter is not

 

considered. Even as a result of the cooling PID calculation device

 

calculates the output value less than this parameter, cooling

 

output is active minimumor OLLC parameter.

COOLING MAXIMUM CONTROL

 

OUTPUT

 

(

It is

 

%

 

of cooling maximum output.

Even as a result of the cooling PID calculation device

 

calculates the output value greater than this parameter,

 

cooling output is active maximum for

 

OULC

 

parameter.

COOLING MINIMUM CONTROL OUTPUT ( 0.0%

,          )

Cooling output can not be active less than this parameter.

Even if this parameter is 0, this parameter is accepted 50

msecs for security.

ANTI-RESET WINDUP

0-SCALE HIGH POINT

(       ,

)UNIT

*

/ (

-

)

While PID operation is running if

-            <= process value <=            +

condition is true, integral value is calculated. If the condition

 

is not true, integral value is not calculated and last

 

calculated integral value is used. If

 

Ar Parameter is

 

selected           , heating proportional band is used for

 

heating PID process instead of

 

Ar Parameter and cooling

 

proportional band is used for cooling PID process instead of

 

Ar Parameter.

SET

 

VALUE

 

OFFSET

((-

 

SCALE

 

HIGH

 

POINT

 

/

 

2)

 

,

 

(SCALE

 

HIGH

 

POINT

 

/

 

2)

 

)Unit

+

 

is

 

used

 

as

 

set

 

value

 

in

 

PID

 

calculations.

 

This

 

parameter

 

is

 

used

 

for

 

shifting

 

the

 

proportional

 

band.

PID

 

OUTPUT

 

OFFSET

(FOR

 

HEATING

 

PID

 

0.0,

 

100.0)%

(FOR

 

COOLING

 

PID

 

-100.0,

 

0.0)%

(FOR

 

HEATING

 

&

 

COOLIN

PID

 

:

 

-100.0,

 

100.0)%

This

 

parameter

 

is

 

added

 

to

 

“Output

 

%”

 

which

 

is

 

calculated

 

at

 

the

 

end

 

of

 

the

 

PID.

OUTPUT

 

OFFSET

 

RELATED

 

TO

 

PID

 

SET

(FOR HEATING PID 0.0, 100.0)%
(FOR COOLING PID -100.0, 0.0)%

(FOR

 

HEATING

 

&

 

COOLIN

PID

 

:

 

-100.0,

 

100.0)%

This

 

parameter

 

is

 

added

 

to

 

the

 

%process

 

output

 

that

 

is

 

calculated

 

at

 

the

 

end

 

of

 

the

 

PID

 

according

 

to

 

process

 

set

 

value

Process Value Low PointAdjustment Parameter

(For TC and RTD input scales)

It can be adjusted -50% to 50% of scale.

Process Value Up PointAdjustment Parameter

(For TC and RTD input scales)

It can be adjusted -50% to 50% of scale.

Содержание m Series

Страница 1: ...ds Programmable ON OFF P PI PD or PID Z OUTPUT 5A 250V 0 4 20 mA V Z Standard Relay Output ADDITIONAL INPUT Extra Analog Input Programmable control or alarm output Electrical Life 100 000 Operation Full Load Extra Relay Output 3A 250V Relay Output Current Input INDICATORS Process Indicators mL PIDC6 10 1 mm Red 4 digit LED Display mL PIDC8 13 2 mm Red 4 digit LED Display Setpoint Indicators mL PID...

Страница 2: ... is of the right size Check front panel gasket position 3 Insert the device through the cutout If the mounting clamps are on the unit remove them before inserting the unit to the panel 4 Insert the unit in the panel cut out from the front side 5 Insert the mounting clamps to the holes that are located on top and bottom sides of the device and tighten the fixing screws until the unit is completely ...

Страница 3: ...y Access Diagram for Technician Parameters C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT Main Operation Screen Operator menu entering screen C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT SET C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT SET Press menu button Press menu changing next Button Enter the password with increment and...

Страница 4: ...Type Low Point Display adjustment 1999 9999 Unit Active if oltage Current input is selected ZV High Point Display adjustment 1999 9999 Unit Active if oltage Current input is selected ZV Display adjustment points 1999 9999 Unit For example This parameter is active if oltage Current is selected In multi point display adjustment operation defined scale is divided into 16 adjustment points is 0 50 mV ...

Страница 5: ...T 0 0 100 0 If heating and cooling PID is used in a system tune operation is performed by heating output Cooling proportional parameter is calculated with heating proportional band value and coefficient P CL P Ht CCoE 100 0 COOLING PROPORTIONAL BAND 000 0 999 9 If Proportional Band Proportional Band 1000 C 0 C and 50 0 ise 100 0 1000 0 50 0 100 0 500 C COOLING INTEGRAL TIME 0000 sec 3600 secs It c...

Страница 6: ... 1 socket is EMI 440 Z Voltage Current input type selection This must be selected since analog input module is in Module 1 socket Input Module Selection MODULE 1 Z Z Voltage Current Voltage Current It is active if input type of Module 1 is selected 0 50mV Z 1999 9999 0 5V Z 1999 9999 0 10V Z 1999 9999 0 20mA Z 1999 9999 4 20mA Z 1999 9999 point position for display It is active if input type of Mo...

Страница 7: ...e When the value is than 9998 is seen on the display It means alarm latching output is selected It is active if logic output function of Output 3 is alarm output 0 9998 Seconds ýoP1 ConF MODULE 2 Configuration Parameters These devices are equipped with an additional Relay i Output plugged into Module 2 socket Defines output function for Module 2 Heating Cooling Logic output It is active if output ...

Страница 8: ...socket Analog Input Modules If you have any of these parameters is observed 2 Sensor Set Point Hýgh Limit sensor scale min 2 Sensor Unit Module 1 or Module 2 socket Analog Input Modules If you have any of these parameters is observed While the motor is completely off the valve fully open While the fully open or fully closed for the pass time required Value between 5 and 600 seconds can be entered ...

Страница 9: ...O2 O3 SV REMOTE RAMP MAN AUTO AT SET 9 The device is powered up the normal does not begin to run and the bottom of the screenAs the side flashing Module 1 and Module 2 slots EMIX10 EMI X30 X40 EMI EMI X50 Analog input modules installed at the same time the event occurs The unit normal to return to work the device energy cut off and Analog Input one of the modules must be removed 10 When power is o...

Страница 10: ... This symbol is used to determine the dangerous situations as a result of an electric shock User must pay attention to these warnings definitely This symbol is used to determine the important notes about functions and usage of the device Company Information Kessler Ellis Products 10 Industrial Way East Eatontown NJ 07724 Phone 800 631 2165 or 732 935 1320 Fax Email Web 732 935 9344 info kep com ww...

Отзывы: