7
out3 ConF: Output-3 Configuration Parameters
Defines output function for Output-3
Heating
Cooling
Logic output
Defines control algorithm of Output-3.
It is active if output function of Output-3 is heating or cooling
ON/OFF control algorithm
PID control algorithm
Hysteresis value for OUT-3.
It can be adjusted from 0% to
50% of defined scale. ( It is active if ON/OFF control is
selected)
It determines operation form of hysteresis.
( It is active if
ON/OFF control is selected)
SV+ HYS/2 and SV- HYS/2
SV and SV+HYS or SV and SV-HYS
In ON/OFF operation, this time must be passed for the output to
be energised again. ( It is active if ON/OFF control is selected)
It determines logic output function of Output-3.
It is active if output function of Output-3 is Lout(Logicoutput)
Alarm output
Manual /Automatic data output
Sensor break alarm output
P
Output is active when the process value is out of the band
which is defined with minimum value of operating scale
And maximum value of operating scale
Output indicates that Ramp/Soak function has finished
Sensor break alarm output for analogue input module in
Module-1or Module-2 socket. ( It is visible if one of analogue
input modules is plugged in Module-1 or Module-2 socket )
If process value is less than minimum value of operating scale
or for analogue input module in Module-1 or Module-2 socket
or greater than maximum value of operating scale or for
analogue input module in Module-1 or Module-2 socket,
process output becomes active.(This parameter is visible if
one of the analogue input modules is plugged in Module-1 or
Module-2 socket)
Measurement input selection for Output-3 alarm output.
This parameter is visible if Logic output function of Output-3 is
Alarm output and one of the analogue input modules is
plugged in Module-1 or Module-2 socket
Alarm output runs according to the process input
Alarm output runs according to the analogue input module
(2nd sensor input) in Module-1 or Module-2 socket.
It determines alarm
It is active if logic output function of Output-3
is alarm output.
Process high alarm
Process low alarm
Deviation high alarm.
Deviation low alarm.
Deviation band alarm.
Deviation
range alarm
IsýtýcýArýzasýAlarmý.
It is active if
V
CT input module is
plugged in Module-1 or Module-2 socket.
Alarm- 3 hysteresis value.
(Scale 0% , scale 50%)Unit
It is active if logic output function of Output-3
Alarm on delay time
(0, 9999)Seconds
It is active if logic output function of Module-1 is alarm output.
Alarm off delay time
When the value is than 9998, is seen on the display.
It means alarm latching output is selected. It is active if
logic output function of Output-3 is alarm output.
(0, 9998)Seconds
ýoP1 ConF: MODUL
E
-
2
Configuration Parameters
These
devices
are
equipped with an additional
Relay
i
Output
plugged in
to
Module-
2
socket.
Defines
output
function
for
Module-
2
Heating
Cooling
Logic output
It is active if output function of Module-1 is heating or cooling.
ON/OFF
PID
Hysteresis value for OUT-
2
.
It
an be adjusted from 0% to
50%
of defined scale. ( It is active if ON/OFF control is selected
. )
It determines operation form of hysteresis.
( ON/OFF )
SV
+
HYS/2
and
SV
-
HYS/2
SV
and
SV+HYS
or
SV
and
SV-HYS
In ON/OFF operation, this time must be passed for the
output to be
logic output function of output module in Module-
2
It is active if output function of Module-
2
is Lout (Logic Output)
Alarm output
Manual /Automatic data output
Sensor break alarm output
Output is active when the process value is out of the band
which is defined with minimum value of operating scale
And maximum value of operating scale
Output indicates that Ramp/Soak function has finished
Sensor break alarm output for
analog
input module in
Module-
1
socket. ( It is visible if one of
analog
input
modules
is plugged in Module-
1
socket )
If process value is less than minimum value of operating
scale for analogue input module in Module-2 socket
or greater than maximum value of operating scale for
analogue input module in Module-2 socket, process output
becomes active.(This parameter is visible if one of the
analogue
input modules is plugged in Module-2 socket)
Measurement input selection for Module-
2
ala
r
m output.
This parameter is visible if Logic output function of Module-
2
is
Alarm output and one of the analogue input modules is
plugged in Module-
1
socket
Alarm output runs according to the process input.
Alarm output runs according to the analogue input module
(2nd sensor input) in Module-
1
socket
MODULE-
2
alarm
It determines alarm type. It is active if logic output function
of
Module-1 is an alarm output.
Process high alarm
Process low alarm
Deviation high alarm
Deviation low alarm
Deviation band alarm.
Deviation
range alarm
Heater failure alarm
does not
apply on these devices
MODULE-
2
Alarm-
2
hysteresis
value.
It is active if logic output function of Module-
2
is an alar
m
output.
Alarm on delay time
It is active if logic output function of Module-
2
is an alar
m
output
(0, 9999)Seconds
Alarm off delay time
Alarm off delay time. It can be adjusted from 0000 to 9998
seconds.When the value is greater than 9998 , is
seen on the display. It means alarm latching output is
selected.
(0, 9998)Seconds
out 2
2
2
2
2
2
2
2
2
2
2