out3 ConF: Output-3 Configuration Parameters

Defines output function for Output-3

Heating
Cooling
Logic output

Defines control algorithm of Output-3.

It is active if output function of Output-3 is heating or cooling
ON/OFF control algorithm
PID control algorithm

Hysteresis value for OUT-3.

It can be adjusted from 0% to

50% of defined scale. ( It is active if ON/OFF control is

selected)

It determines operation form of hysteresis.

( It is active if

ON/OFF control is selected)

SV+ HYS/2 and SV- HYS/2

SV and SV+HYS or SV and SV-HYS

In ON/OFF operation, this time must be passed for the output to

be energised again. ( It is active if ON/OFF control is selected)

It determines logic output function of Output-3.

It is active if output function of Output-3 is Lout(Logicoutput)
Alarm output
Manual /Automatic data output
Sensor break alarm output

P

Output is active when the process value is out of the band

which is defined with minimum value of operating scale

And maximum value of operating scale

Output indicates that Ramp/Soak function has finished
Sensor break alarm output for analogue input module in

Module-1or Module-2 socket. ( It is visible if one of analogue

input modules is plugged in Module-1 or Module-2 socket )
If process value is less than minimum value of operating scale

or for analogue input module in Module-1 or Module-2 socket

or greater than maximum value of operating scale or for

analogue input module in Module-1 or Module-2 socket,

process output becomes active.(This parameter is visible if

one of the analogue input modules is plugged in Module-1 or

Module-2 socket)

Measurement input selection for Output-3 alarm output.

This parameter is visible if Logic output function of Output-3 is

Alarm output and one of the analogue input modules is

plugged in Module-1 or Module-2 socket
Alarm output runs according to the process input
Alarm output runs according to the analogue input module

(2nd sensor input) in Module-1 or Module-2 socket.

It determines alarm

It is active if logic output function of Output-3

is alarm output.
Process high alarm
Process low alarm
Deviation high alarm.
Deviation low alarm.
Deviation band alarm.
Deviation

range alarm

IsýtýcýArýzasýAlarmý.

It is active if

V

CT input module is

plugged in Module-1 or Module-2 socket.

Alarm- 3 hysteresis value.

(Scale 0% , scale 50%)Unit

It is active if logic output function of Output-3

Alarm on delay time

(0, 9999)Seconds

It is active if logic output function of Module-1 is alarm output.

Alarm off delay time

When the value is than 9998,            is seen on the display.

It means alarm latching output is selected. It is active if

logic output function of Output-3 is alarm output.

(0, 9998)Seconds

ýoP1 ConF: MODUL

E

-

Configuration Parameters

These

 devices

are

equipped with an additional 

Relay

i

Output

 

plugged in

to

Module-

2

socket.

Defines

 

output

 

function

 

for

 

Module-

2

Heating
Cooling
Logic output
It is active if output function of Module-1 is heating or cooling.

ON/OFF
PID

Hysteresis value for OUT-

2

.

 

It

 

an be adjusted from 0% to

 

50% 

of defined scale. ( It is active if ON/OFF control is selected

. )

It determines operation form of hysteresis.

 

( ON/OFF )

SV

 

+

 

HYS/2

 

and

 

SV

 

-

 

HYS/2

SV

 

and

 

SV+HYS

 

or

 

SV

 

and

 

SV-HYS

In ON/OFF operation, this time must be passed for the

output to be

logic output function of output module in Module-

2

It is active if output function of Module-

2

 is Lout (Logic Output)

Alarm output
Manual /Automatic data output
Sensor break alarm output

Output is active when the process value is out of the band

which is defined with minimum value of operating scale

And maximum value of operating scale

Output indicates that Ramp/Soak function has finished
Sensor break alarm output for 

analog

 input module in

 

Module-

1

 socket. ( It is visible if one of 

analog

 input

 

modules

is plugged in Module-

1

 socket )

If process value is less than minimum value of operating

scale for analogue input module in Module-2 socket

or greater than maximum value of operating scale for

analogue input module in Module-2 socket, process output

 

becomes active.(This parameter is visible if one of the

 

analogue 

input modules is plugged in Module-2 socket)

Measurement input selection for Module-

2

ala

r

m output.

This parameter is visible if Logic output function of Module-

is

 

Alarm output and one of the analogue input modules is

 

plugged in Module-

socket

Alarm output runs according to the process input.
Alarm output runs according to the analogue input module

 

(2nd sensor input) in Module-

1

 socket

MODULE-

alarm

It determines alarm type. It is active if logic output function

 

of 

Module-1 is an alarm output.
Process high alarm
Process low alarm
Deviation high alarm
Deviation low alarm
Deviation band alarm.
Deviation

 

range alarm

Heater failure alarm

 does not 

apply on these devices

MODULE-

Alarm-

 2 

hysteresis

 

value.

It is active if logic output function of Module-

2

 is an alar

m

 

output.

Alarm on delay time

It is active if logic output function of Module-

2

 is an alar

output

(0, 9999)Seconds

Alarm off delay time

Alarm off delay time. It can be adjusted from 0000 to 9998

seconds.When the value is greater than 9998            , is

seen on the display. It means alarm latching output is

selected.

(0, 9998)Seconds

out 2

2

2

2

2

2

2

2

2

2

2

Содержание m Series

Страница 1: ...ds Programmable ON OFF P PI PD or PID Z OUTPUT 5A 250V 0 4 20 mA V Z Standard Relay Output ADDITIONAL INPUT Extra Analog Input Programmable control or alarm output Electrical Life 100 000 Operation Full Load Extra Relay Output 3A 250V Relay Output Current Input INDICATORS Process Indicators mL PIDC6 10 1 mm Red 4 digit LED Display mL PIDC8 13 2 mm Red 4 digit LED Display Setpoint Indicators mL PID...

Страница 2: ... is of the right size Check front panel gasket position 3 Insert the device through the cutout If the mounting clamps are on the unit remove them before inserting the unit to the panel 4 Insert the unit in the panel cut out from the front side 5 Insert the mounting clamps to the holes that are located on top and bottom sides of the device and tighten the fixing screws until the unit is completely ...

Страница 3: ...y Access Diagram for Technician Parameters C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT Main Operation Screen Operator menu entering screen C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT SET C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT C F V O1 O2 O3 SV REMOTE RAMP MAN AUTO AT SET Press menu button Press menu changing next Button Enter the password with increment and...

Страница 4: ...Type Low Point Display adjustment 1999 9999 Unit Active if oltage Current input is selected ZV High Point Display adjustment 1999 9999 Unit Active if oltage Current input is selected ZV Display adjustment points 1999 9999 Unit For example This parameter is active if oltage Current is selected In multi point display adjustment operation defined scale is divided into 16 adjustment points is 0 50 mV ...

Страница 5: ...T 0 0 100 0 If heating and cooling PID is used in a system tune operation is performed by heating output Cooling proportional parameter is calculated with heating proportional band value and coefficient P CL P Ht CCoE 100 0 COOLING PROPORTIONAL BAND 000 0 999 9 If Proportional Band Proportional Band 1000 C 0 C and 50 0 ise 100 0 1000 0 50 0 100 0 500 C COOLING INTEGRAL TIME 0000 sec 3600 secs It c...

Страница 6: ... 1 socket is EMI 440 Z Voltage Current input type selection This must be selected since analog input module is in Module 1 socket Input Module Selection MODULE 1 Z Z Voltage Current Voltage Current It is active if input type of Module 1 is selected 0 50mV Z 1999 9999 0 5V Z 1999 9999 0 10V Z 1999 9999 0 20mA Z 1999 9999 4 20mA Z 1999 9999 point position for display It is active if input type of Mo...

Страница 7: ...e When the value is than 9998 is seen on the display It means alarm latching output is selected It is active if logic output function of Output 3 is alarm output 0 9998 Seconds ýoP1 ConF MODULE 2 Configuration Parameters These devices are equipped with an additional Relay i Output plugged into Module 2 socket Defines output function for Module 2 Heating Cooling Logic output It is active if output ...

Страница 8: ...socket Analog Input Modules If you have any of these parameters is observed 2 Sensor Set Point Hýgh Limit sensor scale min 2 Sensor Unit Module 1 or Module 2 socket Analog Input Modules If you have any of these parameters is observed While the motor is completely off the valve fully open While the fully open or fully closed for the pass time required Value between 5 and 600 seconds can be entered ...

Страница 9: ...O2 O3 SV REMOTE RAMP MAN AUTO AT SET 9 The device is powered up the normal does not begin to run and the bottom of the screenAs the side flashing Module 1 and Module 2 slots EMIX10 EMI X30 X40 EMI EMI X50 Analog input modules installed at the same time the event occurs The unit normal to return to work the device energy cut off and Analog Input one of the modules must be removed 10 When power is o...

Страница 10: ... This symbol is used to determine the dangerous situations as a result of an electric shock User must pay attention to these warnings definitely This symbol is used to determine the important notes about functions and usage of the device Company Information Kessler Ellis Products 10 Industrial Way East Eatontown NJ 07724 Phone 800 631 2165 or 732 935 1320 Fax Email Web 732 935 9344 info kep com ww...

Отзывы: