UL Listing Requirement
All control panel designs restrict the number of NAC devices installed in circuits based on the rated
current threshold. Some control panel designs further restrict the number of NAC devices installed in
circuits based on device synchronization in addition to the rated current threshold. These control
panel designs can reduce the population of NAC devices below the number of devices that would be
considered for the rated current threshold.
NAC outputs of the Sigma A-CP Fire Control Panel are not limited by conditions other than the
maximum rated current threshold. NAC outputs of the Sigma A-CP Fire Control Panel can operate
combinations of Kentec authorized NAC devices as long as the total load of NAC 1 and NAC 2 does not
exceed 4 A.
The following series of System Sensor NAC devices are compatible for use on the special application
outputs of NAC 1 and NAC 2 when operating each NAC output below 2.5 A:
Name of Series
Environment
Model Series
Description
Mounting
Type
SpectrAlert Advance
Indoor
SPS
Speaker Strobe
Wall
SpectrAlert Advance
Indoor
SPSC
Speaker Strobe
Ceiling
SpectrAlert Advance
Outdoor
SPS (K)
Speaker Strobe
Wall
SpectrAlert Advance
Outdoor
SPSC (K)
Speaker Strobe
Ceiling
SpectrAlert Advance
Indoor
P2
Horn Strobe,
2-Wire
Wall
SpectrAlert Advance
Indoor
P4
Horn Strobe,
4-Wire
Wall
SpectrAlert Advance
Indoor
S
Strobe
Wall
SpectrAlert Advance
Indoor
PC2
Horn Strobe,
2-Wire
Ceiling
SpectrAlert Advance
Indoor
PC4
Horn Strobe,
4-Wire
Ceiling
SpectrAlert Advance
Indoor
SC
Strobe
Ceiling
SpectrAlert Advance
Indoor
H
Horn
Wall/Ceiling
www.acornfiresecurity.com
www.acornfiresecurity.com