5
Turn the Enable Access key to the left to exit Access Level 2.
The Trouble/ Test /Disablement LEDs, Disablement LED and Mode LED are no longer lit.
Disable NAC Outputs
To disable NAC outputs:
1
Turn the Enable Access key to the right to open Access Level 2.
2
Press the mode button to select “db” on the seven segment display.
3
Press Enter to disable all NAC outputs and cause the Disablement and NAC Trouble/ Disabled LEDs to light.
Disable Trouble Contact
To disable a trouble relay contact:
4
Turn the Enable Access key to the right to enter Access Level 2.
5
Move the Write Enable slide-switch to the left to enter Access Level 3.
6
Select configuration code 22
Reference additional disablement options in Functions and Codes of this section.
Alarm Delays
To activate zone alarm delays on the fire control panel:
1
Turn the Enable Access key to the right to enter Access Level 2.
2
Move the Write Enable slide-switch to the left to enter Access Level 3.
The Write Enable slide-switch is located on the lower-right portion of the fascia adjacent
to the Processor Reset button.
The fire control panel beeps three-times to indicate entry in Access Level 3.
The beeping continues to indicate Access Level 3 operation.
Code 00 is displayed on the menu of the Mode LED after entering Access Level 3.
3
Choose an alarm delay code in the 00-09 range and press Enter to set the delay.
A flashing dot is displayed in the lower-right-corner of the Mode LED to identify the set code.
4
Press Mode (+10) on the fascia to scroll from code 00 to 31 on the menu.
www.acornfiresecurity.com
www.acornfiresecurity.com
Содержание Sigma A-CP
Страница 105: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 106: ...www acornfiresecurity com www acornfiresecurity com ...