5
Press Select (+1) on the fascia to scroll from zone code 31 to 38 on the menu.
6
Choose the zone code on the menu and press Enter to program the zone.
A flashing dot is displayed in the lower-right-corner of the Mode LED to identify the set code.
7
Move the Write Enable slide-switch to the right to exit Access Level 3.
8
Select “Ad” in Access Level 2 to add delay to the alarm.
9
Turn the Enable Access key to the left to exit Access Level 2 and return the fire control panel to the Normal
Standby condition.
Reference Default Operation before programming these alarm delay settings.
Relay Operation
The Sigma A-CP Fire Control Panel provides volt free changeover relay contacts for local control and
signaling. The relay contacts are rated for switching signaling circuits only and the maximum ratings
should not be exceeded under any circumstances.
Reference Appendix A, Specifications for relay ratings and operating characteristics.
Relays of the Sigma A-CP Fire Control Panel are common, not programmable and include:
TRBL (Trouble)
The trouble relay is normally energized and will de-energize upon any
trouble condition including total loss of power.
SUPV. (Supervisory)
The supervisory relay energizes during activation of a supervisory condition
on any zone. The relay remains activated until the fire control panel is reset.
FIRE
The fire relay energizes during activation of a fire condition on any zone or
by pressing the sound alarm button in Access Level 2 on the fascia. The
relay remains activated until the fire control panel is reset.
www.acornfiresecurity.com
www.acornfiresecurity.com
Содержание Sigma A-CP
Страница 105: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 106: ...www acornfiresecurity com www acornfiresecurity com ...