INSTALLATION INSTRUCTIONS

CSMRI_F-3732_050813

Content of specification sheets is subject to change; please consult www.kenall.com for current product details. © 2013 Kenall  Mfg. Co.  All rights reserved.

 www. kenall.com 

P: 800-4-Kenall            F: 847-360-1781           1020 Lakeside Drive Gurnee, Illinois 60031    

CUSTOMER ACKNOWLEDGEMENT

Customer acknowledges that these Installation Instructions are part of the product specification, and that the

attached Installation Registration Form will be provided to the installer to sign and return to Kenall after

installation is complete. This signed release is required by Kenall before order will be released into production.

Signature: _________________________________      Date: _________________________________ 

Print Name: _______________________________       Company Name:__________________________

• Disconnect power to all circuits before wiring system.
• Install in accordance with all national, state, and local codes.
• Do not connect to an ungrounded supply.
• Wiring connections must be made internal to the enclosure.
• Failure to install unit on a mechanically-sound surface may result in personal injury, physical damage, or potential 

fire hazard.

• Use installation procedures appropriate for an environment involving MRI and sensitive electronic equipment.
• Read all markings and labels to ensure correct installation of the power supply. Supplemental instructions may be 

located on the enclosure, in addition to this instruction sheet, regarding orientation, or mounting restrictions.

• Read instructions provided with the MedMaster

 MRIPS-312 external power supply for proper installation and 

electrical connection to the lighting system.

IMPORTANT SAFEGUARDS

To prevent 

MRI machine interference, all DC power and dimming signal wiring must be completely shielded within 

grounded aluminum conduit and a suitable 

MRI 

room 

EMI 

filter must be installed on each line.

When using electrical equipment, basic safety precautions should always be followed, including the following:

THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE 

CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. 

SAVE THESE INSTRUCTIONS

Содержание CSMRI Series

Страница 1: ...OUNTING RESTRICTIONS SAVE THESE INSTRUCTIONS INSTALLATION INSTRUCTIONS PREP INSTALLATION SURFACE Disconnect power to all circuits before wiring system Install in accordance with all national state and...

Страница 2: ...age is divided among multiple lightboxes make sure lightbox is oriented toproduce a continuous image It is recommended that the door remain attached to the lightbox housing during installation This wi...

Страница 3: ...supply from the EMI filter to luminaires s using at least 18 AWG wires Class 1 wiring is required Make sure wiring is completely enclosed in grounded aluminum conduit Any gaps regardless of size must...

Страница 4: ...MRIPS 312 instruction sheet and fax to Kenall at 847 360 1781 II Door Opening Closing and Removal Procedure NOTE OPENING THE DOOR DURING NORMAL INSTALLATION IS NOT NECESSARY ALL WIRING SHOULD BE ACCE...

Страница 5: ...for proper engagement of catch hooks before closing door Installing the Door CSMRI22 Lift door by spring clips on one side Engage spring clips on one side to hang vertically Closing the Door With catc...

Страница 6: ...on opposite sides of each other and when installed into the lightbox will put the image in the correct orientation Fasten all hex nuts to retainer brackets Torque all fasteners equally to 12 lb in Re...

Страница 7: ...ed installed in applications for which it is not intended This includes operation in ambient temperatures above stated limits for any length of time Failure by electrical surge shall not be covered un...

Страница 8: ...to an ungrounded supply Wiring connections must be made internal to the enclosure Failure to install unit on a mechanically sound surface may result in personal injury physical damage or potential fi...

Страница 9: ...nduit Installation has no ungrounded unshielded portions of conduit or openings of any size or shape Check here if dimming is not applicable MRI Room EMI filters for the 24VDC supply are of the type i...

Отзывы: