INSTALLATION INSTRUCTIONS
CSMRI_F-3732_050813
GENERAL
• Read instructions provided with the
MedMaster™ MRIPS-312 external power
supply for proper installation and electrical
connection to the lighting system.
INSTALLATION INSTRUCTIONS
• The CleanScene MRI™ lighting system
contains sensitive electronics. Take care
to avoid damage by improper handling or
static electricity discharge (ESD). Either
type of damage could render the
system inoperable.
Lightbox Mounting Procedure
CleanScene MRI™ lightboxes are designed
for either 1” or 1½” (G10 or G15
respectively—see product label) T-bar grid
systems with vertical grid T thickness of less
than ¼”. Grid systems can be installed with
standard 24” x 24”, 24” x 48” or 48” x 48”
centerline grid spacing.
Use the following procedure to install the
lightbox(es) into the ceiling grid:
• Unpack products from the shipping carton.
• Determine where lightbox(es) will be
mounted and note the desired orientation
of graphic images within room.
NOTE: For installations with a multiple-
configuration (the image is divided among
multiple lightboxes), make sure lightbox is
oriented toproduce a continuous image.
• It is recommended that the door remain
attached to the lightbox housing during
installation. This will prevent damage to
internal components, particularly the LED
light sources. All electrical connections are
accessible through the external junction
box located on the top of the
lightbox housing.
GENERAL
• Lift lightbox(es) into ceiling structure using
a recommended minimum of two able-
bodied individuals.
• Lay lightbox(es) into grid.
• Attach support wires between hanger
brackets and ceiling support structure.
• Mount and wire the MRIPS-312 external
power supply per the procedures provided
in the supplementar conduit and DC wiring
to an MRI room EMI filter sized to the
load of the power supply (supplied by
others).completely enclosed in grounded
aluminum conduit. Any gaps, regardless
of size, must be closed and/or wrapped in
copper foil tape.
• If a 0-10V dimmer is to be connected,
install at this time. Dimmer must be
installed outside the shielded MRI
environment with an intermediate MRI
room EMI filter to the luminaire(s). Kenall
recommends using a Leviton
®
IllumaTech
™
IP710 series dimmer or Grafik Eye GRX-TVI
control interface. Contact Kenall for
suitability of using an alternate sink-type
0-10V dimmer.