INSTALLATION INSTRUCTIONS

CSMRI_F-3732_050813

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions 

should always be followed, including the following:

 

THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE 

APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH 

THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND 

THE HAZARDS INVOLVED. DISCONNECT POWER TO ALL CIRCUITS 

BEFORE WIRING FIXTURE. INSTALL IN ACCORDANCE WITH 

ALL NATIONAL, STATE, AND LOCAL CODES. DO NOT CONNECT 

TO AN UNGROUNDED SUPPLY. READ ALL FIXTURE MARKINGS 

AND LABELS TO ENSURE CORRECT INSTALLATION OF FIXTURE. 

SUPPLEMENTAL INSTRUCTIONS MAY BE LOCATED ON THE 

FIXTURE, IN ADDITION TO THIS INSTRUCTION SHEET, REGARDING 

ORIENTATION, OR MOUNTING RESTRICTIONS. 

 

SAVE THESE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

PREP INSTALLATION SURFACE
•  Disconnect power to all circuits before 

wiring system.

•  Install in accordance with all national, 

state, and local codes.

•  Do not connect to an ungrounded supply.

Flange Mounting

•  Wiring connections must be made internal 

to the enclosure.

•  Failure to install unit on a mechanically-

sound surface may result in personal injury, 
physical damage, or potential fire hazard.

•  Use installation procedures appropriate for 

an environment involving MRI and sensitive 
electronic equipment.

CSMRI SERIES

MEDMASTER CLEANSCENE

 

MRI/Imaging Suite Luminaires

•  Read all markings and labels to ensure 

correct installation of the power supply. 
Supplemental instructions may be located 
on the enclosure, in addition to this 
instruction sheet, regarding orientation, or 
mounting restrictions.

•  Read instructions provided with the 

MedMaster™ MRIPS-312 external power 
supply for proper installation and electrical 
connection to the lighting system.

Содержание CSMRI Series

Страница 1: ...OUNTING RESTRICTIONS SAVE THESE INSTRUCTIONS INSTALLATION INSTRUCTIONS PREP INSTALLATION SURFACE Disconnect power to all circuits before wiring system Install in accordance with all national state and...

Страница 2: ...age is divided among multiple lightboxes make sure lightbox is oriented toproduce a continuous image It is recommended that the door remain attached to the lightbox housing during installation This wi...

Страница 3: ...supply from the EMI filter to luminaires s using at least 18 AWG wires Class 1 wiring is required Make sure wiring is completely enclosed in grounded aluminum conduit Any gaps regardless of size must...

Страница 4: ...MRIPS 312 instruction sheet and fax to Kenall at 847 360 1781 II Door Opening Closing and Removal Procedure NOTE OPENING THE DOOR DURING NORMAL INSTALLATION IS NOT NECESSARY ALL WIRING SHOULD BE ACCE...

Страница 5: ...for proper engagement of catch hooks before closing door Installing the Door CSMRI22 Lift door by spring clips on one side Engage spring clips on one side to hang vertically Closing the Door With catc...

Страница 6: ...on opposite sides of each other and when installed into the lightbox will put the image in the correct orientation Fasten all hex nuts to retainer brackets Torque all fasteners equally to 12 lb in Re...

Страница 7: ...ed installed in applications for which it is not intended This includes operation in ambient temperatures above stated limits for any length of time Failure by electrical surge shall not be covered un...

Страница 8: ...to an ungrounded supply Wiring connections must be made internal to the enclosure Failure to install unit on a mechanically sound surface may result in personal injury physical damage or potential fi...

Страница 9: ...nduit Installation has no ungrounded unshielded portions of conduit or openings of any size or shape Check here if dimming is not applicable MRI Room EMI filters for the 24VDC supply are of the type i...

Отзывы: