General specification
Pressure rating
10 PN
Max. flow pressure
7 bar
Min. ambient temperature (storage)
0 °C
Max. ambient temperature (storage)
50 °C
Max. volume flow per FL for PWC
15 l/min
Max. volume flow per FL for PWH
10 l/min
Min. operating temperature PWC
10 °C
Max. operating temperature PWH
70 °C
Max. PWH flush duration per 24 hours
(with PURE and LITE, only guaranteed by correct operation*) 10 min
Max. rel. indoor humidity
65 %
Protection class
IP44
Weight with single port
6 kg
Weight with double port
7 kg
Noise emissions
< 30 dB
Nominal drainpipe diameter
40/50 DN
Hygiene Flush Box dimensions (W x H)
400 x 400 mm
Interference dimensions (W x H x D)
400 x 480 x 98 mm
Reversible cover dimensions (W x H)
393 x 292 mm
Max. depth adjustment with (concealed)
mounting frame
65 mm
Spacing of drinking water connections
219 mm
Size of drinking water connection
3/4 “ G
Aerator set incl. flow limiter
5/10/15 l/min
*) A cold drinking water flush (1 min) must be carried out immediately afterwards!