K°Bloc – Fully welded plate heat exchangers - English Version 2.2 - 01.2016
94
Carry out the following steps:
Carry out the leakage test at the maximum permitted pressure specified
on the name plate.
?
Does the pressure drop?
The pressure on the K°Bloc side to be tested may drop due to compres-
sion of the gas inside the unit or due to a slight maladjustment of the
plates. This does not mean that the K°Bloc is leaking.
Readjust the leakage test pressure and check if the pressure is stable
after half an hour.
?
Are there any leaks?
Attempt to remedy the leaks, using the troubleshooting table, see
chapter „Troubleshooting“ > „Troubleshooting“ (page 99).
Done.
7.6 OUTSIDE CLEANING
Carry out the following steps:
1.
Clean the outside of the K°Bloc at regular intervals.
2.
Retouch scratches and impact damage on the painted surfaces of the
K°Bloc immediately.
The K°Bloc is protected against corrosion and weather.
Done.