Kelvinator Air Conditioning
installation instructions 9
Spanner
Torque
wrench
Piping
Taper nut
Indoor unit piping
Model
Suction
(mm)
Discharge
(mm)
Maximum Maximum
6.4 (1/4")
15
10
6.4 (1/4")
15
10
6.4 (1/4")
20
10
6.4 (1/4")
20
10
6.4 (1/4")
16.0 (5/8")
25
10
6.4 (1/4")
16.0 (5/8")
10
6.4 (1/4")
16.0 (5/8")
25
10
6.4 (1/4")
16.0 (5/8")
25
10
6.4 (1/4")
16.0 (5/8")
25
10
Note:
Connect the connection pipe to indoor unit at first and then
to outdoor unit. Handle piping bending with care. Do not
damage the connection pipe. Ensure that the joint nut is
tightened firmly, otherwise, it may cause leakage.
Installation of outdoor unit
Electric wiring
1 Remove the handle on the right side plate of
outdoor unit.
2 Take off wire cord anchorage. Connect and fix power
connection cord to the terminal board. Wiring should fit
that of indoor unit.
3 Fix the power connection cord with wire clamps and then
connect the corresponding connector.
4 Confirm if the wire has been fixed properly.
5 Reinstall the handle.
For 2.6kW and 3.5kW units:
Air Purging and Leakage Test
1 Connect charging hose of manifold valve to charge end
of low pressure valve (both high/low pressure valves
must be tightly shut).
2 Connect joint of charging hose to vacuum pump.
3 Fully open the handle of Lo manifold valve.
4 Open the vacuum pump for vacuumization. At the
beginning, slightly loosen joint nut of low pressure valve
to check if there is air coming inside. (If noise of vacuum
pump has been changed, the reading of multimeter is 0)
Then tighten the nut.
5 Keep vacuuming for more than 15mins and make sure the
reading of multi-meter is -1.0 10
5
pa (-76cmHg).
6 Fully open high/low pressure valves.
7 Remove charging hose from charging end of low
pressure valve.
8 Tighten lid of low pressure valve. (As shown in below)
Multimeter
-76cmHg
Lo Handle
Charging hose
Hi handle
Charging hose
Low pressure valve
Manifold
Valve
Vacu um pump
Outdoor Condensate Drainage (only for Heat pump unit)
During heating operation, the condensate and defrosting
water should be drained out reliably through the drain hose.
Install the outdoor drain connector in a 25mm hole on the
base plate and attach the drain hose to the connector so
that the waste water formed in the outdoor unit can be
drained out. The hole diameter 25mm must be plugged.
Whether to plug other holes will be determined by the
installer according to actual conditions.
Drain-water hole
Bottom frame
Drain plug
Hose (available commercially,
inner diameter 16mm)
Drain connecter
25
length(m)
Height(m)
12.7 (1/2")
12.7 (1/2")
12.7 (1/2")
12.7 (1/2")
For 5.3kW, 6.2kW, 7.0kW and 8.8kW units:
KSE26CRC
KSE26HRC
KSE35CRC
KSE35HRC
KSE53HRC
KSE62HRC
KSE70CRC
KSE70HRC
6.4 (1/4")
16.0 (5/8")
25
10
KSE88HRC
KSE88CRC
Handle
yellow-
black
blue
2
N(1)
3
indoor unit connection
green
yellow-
white
black
blue
brown
blue
2
N(1)
3 4 5
indoor unit connection
green
2.6kW,3.5kW Cool only type
2.6kW,3.5kW Cool and Heat type
violet
orange
7.0 kW,8.8 kW Cool only type
6.2 kW,7.0 kW,8.8 kW Cool and Heat type
5.3kW Cool and Heat type
yellow-
brown
black
blue
white
2
N(1)
3 6
indoor unit connection
green
Handle
yellow-
brown
black
blue
2
N(1)
3
indoor unit connection
green
1
3
2
X1
X2
white