KeepRite N4A3 Скачать руководство пользователя страница 9

INSTALLATION INSTRUCTIONS

R

410A Split System Air Conditioner

421 01 5100 01

9

ELECTRICAL WIRING

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis-

connect device could result in personal injury or

death.
Before installing, modifying or servicing system,

turn OFF the main (remote) electrical disconnect

device. There may be more than one disconnect

device.

The supply voltage must be 208/230 volts (197 volt mini-

mum to 253 volts maximum) 60 Hz single phase.
Outdoor units are approved for use with copper conduc-

tors only. Do not use aluminum wire.
Refer to unit rating plate for minimum circuit ampacity and

circuit protection requirements.

Grounding

Permanently ground unit in accordance with the National

Electrical Code and local codes or ordinances. Use a cop-

per conductor of the correct size from the grounding lug in

control box to a grounded connection in the service panel

or a properly driven and electrically grounded ground rod.

Wiring Connections

Make all outdoor electrical supply (Line Voltage) connec-

tions with raintight conduit and fittings. Most codes re-

quire a disconnect switch outdoors within sight of the unit.

Consult local codes for special requirements.
Route electrical supply (Line Voltage) wiring through

knockout hole in bottom of Control Box. Connect wires to

Contactor and Ground Lug according to Wiring Diagram

on unit. Also refer to Figure 10.
Route thermostat wiring through rubber grommet in bot-

tom of Control Box. Low voltage lead wires are provided in

the control box for connection to thermostat wires (use

wire nuts). Refer to Wiring Diagram on unit and Figure 11

for low voltage wiring examples.

NOTE:

 Use No. 18 AWG (American Wire Gage) color

coded, insulated (35 

°

C minimum) wire. If thermostat is

located more than 100 feet (30.5 m) from unit as mea-

sured along the control voltage wires, use No. 16 AWG

color

coded wires to avoid excessive voltage drop.

Figure 10

Electrical Supply (Line Voltage)

Connections

DISCONNECT

PER NEC AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

11

23 or 13

L1

L2

Figure 11

Typical Thermostat Connections

24 VAC HOT

24 VAC COM

R

C

G

W/W1

Y/Y2

R

C

C

THERMOSTAT

FURNACE

Y

G

W

HEAT STAGE 1

COOL STAGE 1

INDOOR FAN

AIR CONDITIONER

24 VAC HOT

24 VAC COM

R

C

G

W/W1

Y/Y2

R

C

C

THERMOSTAT

FAN COIL

Y

G

W2

HEAT STAGE 1

COOL STAGE 1

INDOOR FAN

AIR CONDITIONER

START

UP PROCEDURE

1. Set indoor thermostat selector switch to OFF.
2. Turn ON all electrical disconnect devices.
3. If unit has a crankcase heater, energize the heater

and wait 24 hours before proceeding.

4. Set indoor thermostat at desired temperature.  Be

sure setpoint is below indoor ambient temperature

or thermostat will not call for cooling.

5. Set indoor thermostat selector switch to COOL.

Operate unit for minimum 10 minutes, then check

the system refrigerant charge.

Содержание N4A3

Страница 1: ... this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Inspect New Unit 2 Safety Considerations 2 Location 2 Clearances 2 3 Unit Support 4 Refrigera...

Страница 2: ...es vents or bed room windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit away from areas where heat lint or exhaust fumes will be discharged onto unit as from dryer vents Locate unit away from recessed or confined areas where recirculation of discharge air may occ...

Страница 3: ...stem Air Conditioner 421 01 5100 01 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service 24 Service 24 Service 4 4 wide fence 18 18 ...

Страница 4: ...hen unit is to be installed on a bonded guaran teed roof a release must be obtained from the building owner to free the installer from all liabilities C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the knockouts in the base pan and install tie down bolts through the holes refer to Figure 2 Contact local distributor for hurricane hold down details an...

Страница 5: ... sealed deoxidized copper refrigeration tubing Do not use copper water pipe Do not remove rubber plugs or caps from copper tubing until connections are ready to be made Be extra careful when bending refrigeration tubing Tub ing can kink easily and if this occurs the entire length of tubing must be replaced Figure 4 R 410A Line Set Tube Diameter Liquid Tube Always a dia Model Size Service Valve Fit...

Страница 6: ...n lines separate Refer to Figure 5 Figure 5 Routing and Suspending Refrigerant Lines INSULATION SUCTION TUBE LIQUID TUBE OUTDOOR WALL INDOOR WALL LIQUID TUBE SUCTION TUBE INSULATION CAULK HANGER STRAP AROUND SUCTION TUBE ONLY JOIST 1 MIN THROUGH THE WALL SUSPENSION CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improp er product operation Do not bury more than 36 of lin...

Страница 7: ...emery cloth or steel brush Remove any grit or debris Insert line set tube ends into service valve tube stubs Apply heat absorbing paste or heat sink product between service valve and joint Wrap service valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage Br...

Страница 8: ...moisture 5 Repeat this procedure as indicated in Figure 9 6 After the final evacuate sequence confirm there are no leaks in the system If a leak is found repeat the entire process after repair is made Figure 9 Triple Evacuation Sequence CHECK FOR TIGHT DRY SYSTEM IF IT HOLDS DEEP VACUUM EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHARGE SYSTEM BREAK VACUUM WITH DRY NITROGEN EVACUATE WAIT...

Страница 9: ...ontactor and Ground Lug according to Wiring Diagram on unit Also refer to Figure 10 Route thermostat wiring through rubber grommet in bot tom of Control Box Low voltage lead wires are provided in the control box for connection to thermostat wires use wire nuts Refer to Wiring Diagram on unit and Figure 11 for low voltage wiring examples NOTE Use No 18 AWG American Wire Gage color coded insulated 3...

Страница 10: ...OTE When adding refrigerant charge in liquid form using a flow restricting device into the suction port If the measured liquid line temperature is lower than the chart number reclaim refrigerant to raise the measured temperature Tolerance is 3 F Figure 12 R 410A Required Liquid Line Temperature F Measured Liquid Pressure psig Rating Plate required Subcooling Temperature F Measured Liquid Pressure ...

Страница 11: ...thout the RED R low voltage lead wire connected The Comfort Alert device operates by monitoring the compressor power leads and the thermostat demand sig nal Y terminal It draws constant 24 VAC power at the R and C terminals Figure 13 Comfort Alertt Diagnostics some models R Y C 24 VAC Common Thermostat Demand 24 VAC Hot Compressor Wires Pass Through Holes 3 R S C Power LED Alert LED Trip LED MAINT...

Страница 12: ...forma tion 4 If low pressure switch present go to Flash Code 1 informa tion Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor bearings are seized Yellow ALERT Flash Code 5 Open Circuit 1 Outdoor unit power disconnect is open 2 Compressor circuit breaker or fu...

Страница 13: ...C refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certain plastics and roofing materials Wrap all filter driers and se...

Отзывы: