KeepRite N4A3 Скачать руководство пользователя страница 8

INSTALLATION INSTRUCTIONS

R

410A Split System Air Conditioner

8

421 01 5100 01

Deep Vacuum Method

The deep vacuum method requires a vacuum pump ca-

pable of pulling a vacuum to 500 microns and a vacuum

gauge capable of accurately measuring this vacuum lev-

el. The deep vacuum method is the most positive way of

assuring a system is free of air and water.
Watch the vacuum gauge as the system is pulling down.

The response of the gauge is an indicator of the condition

of the system (refer to Figure 8).
With no leaks in the system, allow the vacuum pump to

run for 30 minutes minimum at the deep vacuum level.

Figure 8

Deep Vacuum Gauge Response

and System Conditions

500

MINUTES

0

1

2

4

6

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET

TIGHT

DRY SYSTEM

2000

M

ICRONS

2500

3000

3500

4000

4500

5000

3

7

5

Triple Evacuation Method

The triple evacuation method should only be used when

system does not contain any water in liquid form and vac-

uum pump is only capable of pulling down to 28 inches of

mercury. Refer to Fig. 9 and proceed is as follows:

1. Pull system down to 28 inches of mercury and al-

low pump to continue operating for an additional 15

minutes.

2. Close manifold valves or valve at vacuum pump

and shut off vacuum pump.

3. Connect a nitrogen cylinder and regulator to sys-

tem and fill with nitrogen until system pressure is 2

psig.

4. Close nitrogen valve and allow system to stand for

1 hour. During this time, dry nitrogen will diffuse

throughout the system absorbing moisture.

5. Repeat this procedure as indicated in Figure 9.
6. After the final evacuate sequence, confirm there

are no leaks in the system. If a leak is found, repeat

the entire process after repair is made.

Figure 9

Triple Evacuation Sequence

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHARGE SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

I. OPENING SERVICE VALVES

Outdoor units are shipped with a refrigerant charge

sealed in the unit. Opening the service valves releases

this charge into the system.

NOTE:

 Open the Suction service valve first. If the Liquid

service valve is opened first, oil from the compressor may

be drawn into the indoor coil TXV, restricting refrigerant

flow and affecting operation of the system.
Remove Suction service valve cap and insert a hex

wrench into the valve stem. Hold the valve body steady

with an end

wrench and back out the stem by turning the

hex wrench counterclockwise. Turn the stem until it just

contacts the rolled lip of the valve body.
After the refrigerant charge has bled into the system,

open the Liquid service valve.

NOTE:

 These are not back

seating valves. It is not nec-

essary to force the stem tightly against the rolled lip.
The service valve cap is a primary seal for the valve and

must be properly tightened to prevent leaks. Make sure

cap is clean and apply refrigerant oil to threads and seal-

ing surface on inside of cap.
Tighten cap finger tight and then tighten additional 

 of a

turn (1 wrench flat) to properly seat the sealing surfaces.

J. GAUGE PORTS

Check for leaks at the schrader ports and tighten valve

cores if necessary. Install plastic caps finger tight.

Содержание N4A3

Страница 1: ... this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Inspect New Unit 2 Safety Considerations 2 Location 2 Clearances 2 3 Unit Support 4 Refrigera...

Страница 2: ...es vents or bed room windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit away from areas where heat lint or exhaust fumes will be discharged onto unit as from dryer vents Locate unit away from recessed or confined areas where recirculation of discharge air may occ...

Страница 3: ...stem Air Conditioner 421 01 5100 01 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service 24 Service 24 Service 4 4 wide fence 18 18 ...

Страница 4: ...hen unit is to be installed on a bonded guaran teed roof a release must be obtained from the building owner to free the installer from all liabilities C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the knockouts in the base pan and install tie down bolts through the holes refer to Figure 2 Contact local distributor for hurricane hold down details an...

Страница 5: ... sealed deoxidized copper refrigeration tubing Do not use copper water pipe Do not remove rubber plugs or caps from copper tubing until connections are ready to be made Be extra careful when bending refrigeration tubing Tub ing can kink easily and if this occurs the entire length of tubing must be replaced Figure 4 R 410A Line Set Tube Diameter Liquid Tube Always a dia Model Size Service Valve Fit...

Страница 6: ...n lines separate Refer to Figure 5 Figure 5 Routing and Suspending Refrigerant Lines INSULATION SUCTION TUBE LIQUID TUBE OUTDOOR WALL INDOOR WALL LIQUID TUBE SUCTION TUBE INSULATION CAULK HANGER STRAP AROUND SUCTION TUBE ONLY JOIST 1 MIN THROUGH THE WALL SUSPENSION CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improp er product operation Do not bury more than 36 of lin...

Страница 7: ...emery cloth or steel brush Remove any grit or debris Insert line set tube ends into service valve tube stubs Apply heat absorbing paste or heat sink product between service valve and joint Wrap service valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage Br...

Страница 8: ...moisture 5 Repeat this procedure as indicated in Figure 9 6 After the final evacuate sequence confirm there are no leaks in the system If a leak is found repeat the entire process after repair is made Figure 9 Triple Evacuation Sequence CHECK FOR TIGHT DRY SYSTEM IF IT HOLDS DEEP VACUUM EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHARGE SYSTEM BREAK VACUUM WITH DRY NITROGEN EVACUATE WAIT...

Страница 9: ...ontactor and Ground Lug according to Wiring Diagram on unit Also refer to Figure 10 Route thermostat wiring through rubber grommet in bot tom of Control Box Low voltage lead wires are provided in the control box for connection to thermostat wires use wire nuts Refer to Wiring Diagram on unit and Figure 11 for low voltage wiring examples NOTE Use No 18 AWG American Wire Gage color coded insulated 3...

Страница 10: ...OTE When adding refrigerant charge in liquid form using a flow restricting device into the suction port If the measured liquid line temperature is lower than the chart number reclaim refrigerant to raise the measured temperature Tolerance is 3 F Figure 12 R 410A Required Liquid Line Temperature F Measured Liquid Pressure psig Rating Plate required Subcooling Temperature F Measured Liquid Pressure ...

Страница 11: ...thout the RED R low voltage lead wire connected The Comfort Alert device operates by monitoring the compressor power leads and the thermostat demand sig nal Y terminal It draws constant 24 VAC power at the R and C terminals Figure 13 Comfort Alertt Diagnostics some models R Y C 24 VAC Common Thermostat Demand 24 VAC Hot Compressor Wires Pass Through Holes 3 R S C Power LED Alert LED Trip LED MAINT...

Страница 12: ...forma tion 4 If low pressure switch present go to Flash Code 1 informa tion Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor bearings are seized Yellow ALERT Flash Code 5 Open Circuit 1 Outdoor unit power disconnect is open 2 Compressor circuit breaker or fu...

Страница 13: ...C refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certain plastics and roofing materials Wrap all filter driers and se...

Отзывы: