E10 Smart Energy Meter
Set a fixed IP address for your Energy meter
V1.01
9
© KEBA 2023
Modbus Mechanic - manually set a new IP address
1) Open the tool and enter the
IP address
previously shown in the “Ad-
vanced IP Scanner” tool for the KeContact E10 into the field “
IP
”.
2) Also enter
Port „502“
and
Node „1“
.
3) Switch the function to “
Write Holding Registers
”.
4) Enter
259
in the Register field.
5) Enter the first value of the desired IP address into the
Write value
field
(e.g. 192) and click “
Transmit packet
”.
6) Repeat this process also for Register
260-262
.
Example: Write IP address 192.168.10.240
Write value
Register 259
192
Register 260
168
Register 261
42
Register 262
254
Subnet mask
If necessary the subnet mask can be changed via Register 263-266. In most
cases 255.255.255.0 is ok.