E10 Smart Energy Meter
Set a fixed IP address for your Energy meter
V1.01
8
© KEBA 2023
2) Also enter
Port „502“
and
Node „1“
.
3) Switch the function to “
Read Holding Registers
” and set the
Data
value type
to “
Unsigned Int16
”.
Read out current IP settings
1) Enter
259
in the Register field and click “
Transmit packet
”. This should
show the first value of the currently set IP address. If an error is shown,
check if the IP address of the KeContact E10 is correctly set. If not
restart and / or reset the KeContact E10.
2) Repeat this process also for Register
260-262
.
Example: Read out IP address 192.168.0.137
Response value
Register 259
192
Register 260
168
Register 261
0
Register 262
137
Example: Read out subnet mask 255.255.255.0
Response value
Register 263
255
Register 264
255
Register 265
255
Register 266
0
DHCP assignment
Response value
Register 267
1 = enabled
0 = disabled