34
Control circuit
4.3.5.1 External supply
Using the external supply, the control board, I/Os, fieldbus, sensors (temperatures, humidity,
mounting orientation) and the internal fan remain in operation even if the power unit is discon-
nected.
Uin
0Vin
U
Input
Uin
Specification
U
in
: 24 V ±10 %
Terminals
0Vin X2A.35
Uin X2A.36
Current consumption:
Own use 0.65 A
+ load currents at DO 0 ... DO 8
+ load currents at X2B.1/3 ... 31
+ load currents at X3A and X3B
Figure 20: External supply of the control board
4.3.5.2 Digital outputs
All outputs are short-circuit proof. They are suitable for inductive loads (without free-wheeling
diode up to 300 mJ max.).
The sum of the load currents at the 24 V outputs of the control card (DO 0...DO 8, X2B.1/3...31
and X3A und X3B) must not exceed 3.4 A.
DO 0...7
0V
I
L
max
Specification
U: 24 Vdc
ILmax: 250 mA
Terminals
DO
0…7
X2A.18/20…32
0 V X2A.17/19…31
Figure 21: Digital outputsDO 0…DO 7
DO 8
0V
I
L
max
Specification
U: 24 Vdc
ILmax 2 A
Terminals
DO 8 X2A.34
0 V X2A.33
Figure 22: Digital output DO 8