66
cONNecTION OF THe POWer UNIT
4.2.5.2 Terminal block X1A motor connection
Name
Function
Terminal connec-
tion
Tightening
torque
crimp
connector
dimension
type
Max. num-
ber of con-
ductors
1)
U
Motor connection
8 mm stud for
M8 crimp connec-
tor
10...15 Nm
88...132 lb inch
1
For IEC: 2
For UL: 2
V
W
Figure 25: Terminal block X1A motor connection
1)
From 50mm² only one conductor allowed
crimp connector dimension
Type 1
Max. width
l / mm
24
Max. shaft length
l / mm
46
Max. diameter
l / mm
19
Table 32:
Crimp connector dimension motor connection
NOTICE
Short circuit due too low air and creepage distances!
►
The pressing of the crimp connectors must point upwards when
connecting 95 mm² cables!