DeVIce DATA OF THe 400 V DeVIceS
3.2.3 Input and output currents/ overload
Device size
21
22
23
24
Rated input current @
U
N
=
400V
1)
I
IN
/ A
99
126
158
189
Rated input current @
U
N_UL
=
480V
1)
I
IN_UL
/ A
85
106
128
162
Table 12:
Input currents of the 400 V devices
1)
The values resulting from rated operation with B6 rectifier circuit and mains choke 4% U
k
.
Device size
21
22
23
24
Rated output current
@
U
N
=
400V
I
N
/ A
90
115
150
180
Rated output current
@
U
N_UL
=
480V
I
N_UL
/ A
77
96
124
156
Rated output overload (60 s)
1)
I
60s
/ %
150
Overload current
1)
I
OL
/ %
=>
„3.2.3.1 Overload characteristic (OL)“
Software current limit
1) 2)
I
lim
/ %
150
Overcurrent
1)
I
OC
/ %
180
Table 13:
Output currents of the 400 V devices
1)
The values refer in % to the rated output current I
N
.
2)
Limitation of the current setpoint in closed-loop operation. This setpint limit is not active in v/f operation.
Output voltages and frequencies
Output voltage at AC supply
1)
U
out
/ V
0…U
N_ac
Output frequency
2)
f
out
/ Hz
0…599
Output phase
3
Table 10:
Output voltages and frequencies of the 400V devices
1)
The voltage to the motor is dependent on the actual input voltage and the control method
„Example of the calculation of the possible motor voltage:“
).
2)
The output frequency is to be limited in such a way that it does not exceed 1/10 of the switching
frequency. Devices with higher max. output frequency are subject to export restrictions and are
only available on request.
3.2.2.1 Example of the calculation of the possible motor voltage:
The motor voltage for dimensioning of the drive is depending on the used components.
The motor voltage reduces according to the following table:
component
reduction / % example
Mains choke U
k
4
Open-loop drive converter with mains- and motor choke
at non-rigid supply system:
400 V mains voltage (100%) - 36 V reduced voltage (11 %)
= 356 V motor voltage
Drive converter open-loop
4
Drive converter closed-loop
8
Motor choke U
k
1
Non-rigid supply system
2
Table 11:
Example of the calculation of the possible motor voltage: