GB - 20
Safety Function STO
connected drive occurs via transformation coupling of the input voltage. This ensures at input
voltage loss that no supply of the opto-couplers is possible. If the opto-couplers are not longer
supplied, no IGBT can be controlled and thus no energy can be supplied to the drive.
The two channels are reached by way that input STO1 prevents the voltage supply (VTRO)
of the upper opto-couplers of the inverter bridge and input STO2 the lower opto-couplers
(VTRU).
Technical data of the STO function
Maximum ON delay (U
IN
= 15V)
7 ms
Maximum OFF delay (U
IN
=30 V) at
… active modulation
10 ms
… inactive modulation until a safe condition of the driver voltage is reached
50 ms