![KBR multimess F144-2-LED-ESMS 4 Series Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/kbr/multimess-f144-2-led-esms-4-series/multimess-f144-2-led-esms-4-series_user-manual-technical-parameters_659469080.webp)
Rev. 3.00
22067_EDEBD
A0239-3617-3_EN
80
KBR multimess F144-2-LED-ESMS...-4
Continued
Active
energy
Calculation
W (HT/LT); P
average max. of a measurement period
Units
[Wh; kWh; MWh];
display is switched automatically
Measuring range 0.0kWh to 9999999999.9kWh
Reactive
energy
Calculation
W
React
(HT/LT)
p
ind. or cap. Q
average max. of a measurement
period
;
Units
[varh; kvarh; Mvarh]; display is switched automatically
Measuring range 0.0kvarh to 9999999999.9kvarh
Harmonics
Distortion factor
(THD) for voltage
Voltage: DF-UL1; DF-UL2; DF-UL3,
Partial distortion
factors
3rd; 5th; 7th; 9th; 11th; 13th; 15th; 17th
and 19th Harmonics of the voltage
Units
[%]
Measuring range 0.00% to 100%
Current
harmonics
Current
harmonics
Current
harmonics total
3rd; 5th; 7th; 9th; 11th; 13th; 15th; 17th and 19th
Harmonic for each phase of current: I
TotL1
; I
TotL2
; I
TotL3
for
each phase separately
Units
[A]
Measuring range 0.00A to 999.9kA
12.2 Measurement accuracy
Current
± 0.5 % / ± 1 digit
Voltage
± 0.5 % / ± 1 digit
Apparent power
± 1 % / ± 1 digit
Active power
± 1 % / ± 1 digit
Reactive power
± 1 % / ± 1 digit
Power factor
± 1 % / ± 1 digit
Frequency
± 0.1 Hz / ± 1 digit
Technical data