Terminal
36 and 37:
Synchronization input
A floating contact, e.g. from the energy supplier, can be connect-
ed to this input to synchronize the measurement period
38 (-) and 39 (+):
Tariff input
A floating contact, e.g. from the energy supplier, can be con-
nected to this input to switch from high to low tariff.
60, 61, 62 and 63:
Analog outputs
Various parameters can be output as analog values, between
0-20 mA or 4-20 mA and between 0-10 V or 2-10 V. Depending
on which parameter should be output, you can assign a certain
phase (L1, L2, L3) or its total value to the analog output.
Installation and electrical connection