V2.01
25361_EDEBD
A0281-2320-1_EN
64
Example Modbus RTU
Request:
01 04 00 01 00 06 21 C8
in which
01
Device address
04
Command
00 01
Read voltage from register 0x0002 (in accordance with Modbus definition,
the required address must be set to -1 in the request telex)
00 06
Read 6 registers, i.e. read 3 data points
21 C8
CRC code
Response:
01 04 0C 43 6B 5A B4 42 DC 67 20 42 48 0C 63 AF 7C
in which
01
Device address
04
Command
0C
12 data bytes
43 6B 5A B4
Voltage
235.35 V
42 DC 67 20
Current
110.20 A
42 48 0C 63
Network frequency
50.012 Hz
AF 7C
CRC code
Data point description for the Modbus protocol