menu parameters have been set correctly.
To activate learning mode, press
U
, change the setting to Yes by pressing
V
, then press
X
to confirm.
The auto configuration then automatically sets the stage powers and discharge times,
but these values need to be checked once the learning process has been completed to
ensure that they are correct.
NOTE
If an error occurs in auto configuration mode (harmonics exceeding the limit, measuring
voltage too high, missing measuring voltage), the process is interrupted and "Auto con-
figuration mode – Error" is displayed. Auto configuration mode can be restarted once the
cause of the error has been rectified.
System function test:
A function test should be performed after all values have been programmed step by step,
by disconnecting the controller from the power supply for a few seconds.
The controller should start automatically after it is reconnected to the power supply. If
the cosφ voltage is read in the start menu immediately after switching it on, the value for
cosφ should be low and inductive. The controller then starts to switch on the individual
capacitor stages.
The cosφ, which can be read in the start menu, should have risen in comparison to its pre-
vious value, or it should rise when additional stages are switched on. If the compensation
system is designed correctly, the controller should compensate to the set target cos phi
after a while.