V2.01
25361_EDEBD
A0281-2320-1_EN
12
Control and display panel
Stage switching mode:
Automatic
Sampling rate:
Automatic
Harmonics monitoring:
Activated by set limit
Limit THD:
8%
Stage power:
Not set
Max. stage pow. per switch. cycle 0 kVar
Thyristor discharge time:
20 ms
Contactor discharge time:
180 sec.
Password:
No password
(9999, meaning all functions are accessible)
Language display:
English
Contrast setting:
4
Brightness setting:
5
Dimmer brightness:
0
Low load limit:
15 mA
Low load delay:
60 minutes
Temperature measurement:
On
Output 12 as stage or fan:
Fan
Alarm relay as error message
or fan:
Error message
Fan switch-on temperature:
> 28 °C
Fan switch-off temperature:
< 23 °C
System switch-off temperature:
> 48°C
System switch-on temperature:
< 43°C
Learning mode menu display:
Off
Key sounds:
On
Error message dialog after reset:
No measuring voltage:
Message and alarm relay
No stage power:
Message and alarm relay
Facility too small:
Message and alarm relay
THD too high:
Message and alarm relay
Operating cycle limit exceeded:
Message and alarm relay
No measuring current:
Message and alarm relay
Low load operation:
Message and alarm relay
Temperature switch-off:
Message and alarm relay
Содержание F144-MS-1V1C6-6RO-6DO-3
Страница 67: ...Notes V2 01 25361_EDEBDA0281 2320 1_EN 67 ...