KBAC SERIES INSTALLATION AND OPERATION MANUAL 

4 – INTRODUCTION   

Thank you for purchasing the KBAC Adjustable Frequency Drive. KB Electronics, Inc. is committed to providing total customer satisfaction by 
producing quality products that are easy to install and operate. The KBAC is manufactured with surface mount components incorporating 
advanced circuitry and technology. 
 
The drives are variable speed controls housed in a rugged NEMA 4X / IP65 washdown and watertight die-cast aluminum enclosure. They are 
designed to operate 208 – 230 and 400/460 Volt 50 & 60 Hz 3-phase AC induction motors from subfractional thru 10 HP. The sine wave 
coded Pulse Width Modulated (PWM) output operates at a carrier frequency of 16 kHz which provides high motor efficiency and low noise. 
Adjustable Linear Acceleration and Deceleration are provided, making the drive suitable for 
soft-start applications. 
 
Due to its user-friendly design, the KBAC AC drive is easy to install and operate. Tailoring to specific applications is accomplished with 
selectable jumpers and trimpots, which eliminate the computer-like programming required on other drives. However, for most applications no 
adjustments are necessary. 
 
Main features include adjustable RMS Current Limit and I

2

t Motor Overload Protection (UL approved as an electronic overload protector for 

motors). In addition, Adjustable Slip Compensation with Static Auto-Tune and Boost provides high torque and excellent load regulation over a 
wide speed range. Power Start™ delivers over 200% motor torque to ensure start-up of high frictional loads. Electronic Inrush Current Limit 
(EICL™) eliminates harmful AC Line inrush current. A Run/Fault Relay is provided, which can be used to turn equipment on or off, to signal a 
warning if the drive is put into the Stop Mode, or if a fault has occurred. The drive is suitable for machine or variable torque (HVAC) 
applications. Also, a jumper is provided for selection of Regenerative or DC Injection Braking. 
 
Standard front panel features include Diagnostic LEDs for "Power On" and "Drive Status", a Start/Stop Switch, and a Main Speed 
Potentiometer. Other features include a Barrier Terminal Block to facilitate wiring of the AC Line and motor, adjustable trimpots (MIN, MAX, 
ACCEL, DECEL, COMP, CL, JOG, BOOST), customer selectable jumpers (Line Voltage (dual voltage models only)), Motor Horsepower, 
Automatic Ride-Through / Manual Start, Motor Frequency, Frequency Multiplier, Fixed/Adjustable Boost, Regenerative / Injection Braking, 
"Run" or "Fault" Output Relay Operation, NO/NC Stop Contact, Constant/Variable Torque, Switching Frequency, and GFCI operation          
(Third Generation (3G) drives only). 
 
Optional accessories include: Forward-Stop-Reverse Switch, On/Off AC Line Switch, Run-Stop-Jog Switch, Signal Isolator, Auto/Manual 
Switch, Class A AC Line Filter, Multi-Speed Board, and Liquidtight Fittings. A connector is provided for easy installation of accessories. 
Custom software: all models can be factory programmed for applications which require special timing, PLC functions, and GFCI operation. 
 
 

4.1 – STANDARD FEATURES 
Industrial Duty Die-Cast Aluminum Case with Hinged Cover:

 Available in dark gray finish or FDA approved white finish. 

 

Simple to Operate:

 Does not require programming. Uses trimpots and jumpers, which are factory set for most applications. 

Motor HP Selection Jumper (J2): Allows the drive to be used on a wide range of motors without recalibration. 

 

Switching Frequency and GFCI Selection Jumper (J12):

 Allows the drive to be operated at 8 kHz or 12 kHz and on Standard (G1) or 

Sensitive (G2) GFCIs. (Third Generation (3G) drives only.) 

 

Diagnostic LEDs:

 Power on (POWER) and drive status (STATUS). 

 

Run/Fault Relay Output Contacts:

 Can be used to turn equipment on or off, to signal a warning if the drive is put into the Stop Mode, or a 

fault has occurred. 

 

Start/Stop Switch:

 Provides electronic start and stop functions. 

 

Barrier Terminal Block:

 Facilitates wiring of motor, AC Line, and Run/Fault Relay Output Contacts. 

 

Jumper Selection of Drive Output Frequency:

 Increases the motor speed up to two times the rated RPM. 

 

Ride-Through:

 Provides smooth recovery to the previous set speed during a momentary power loss (of less than 2 seconds). 

 

Holding Torque at Zero Speed: 

Resists motor shaft rotation when the drive is in Stop Mode. 

 

Adjustable Trimpots: 

Maximum Speed (MAX), Minimum Speed (MIN), Acceleration (ACCEL), Deceleration (DECEL), DC Injection Brake 

(DECEL), Boost (BOOST), Current Limit (CL), Jog (JOG), Slip Compensation (COMP).  

 

Selectable Jumpers: 

AC Line Input Voltage (J1 – KBAC-24D, 27D only), Motor Horsepower (J2), Automatic Ride-Through or Manual Start 

(J3), Frequency Multiplier (J4), Motor Frequency (J5), Fixed or Adjustable Boost (J6), Regeneration or DC Injection Braking (J7), "Run" or 
"Fault" Output Relay Operation (J8), Normally Open or Closed Stop Contact (J9), Constant or Variable Torque (J10), Switching Frequency 
and GFCI (J12 – Third Generation (3G) drives only). 

 
 

4.2 – PEERFORMANCE FEATURES 
Power Start™:

 Provides more than 200% starting torque which ensures startup of high frictional loads. 

 

Slip Compensation with Static Auto-Tune and Boost:

 Provides excellent load regulation over a wide speed range. 

 

Speed Range:

 60:1. 

 
 

4.3 – PROTECTION FEATURES 
Motor Overload (I

2

t) with RMS Current Limit:

 Provides motor overload protection which prevents motor burnout and eliminates nuisance 

trips. UL approved as an electronic overload protector for motors. 

 

Electronic Inrush Current Limit (EICL™):

 Eliminates harmful Inrush AC Line current during startup. 

 

Short Circuit:

 Shuts down the drive if a short circuit occurs at the motor (phase-to-phase). 

 

Regeneration:

 Eliminates tripping due to high bus voltage caused by rapid deceleration of high inertial loads. 

 

Undervoltage and Overvoltage:

 Shuts down the drive if the AC Line input voltage goes above or below the operating range. 

 

MOV Input Transient Suppression:

 Protects the drive components against damaging voltage spikes on the AC Line. 

 

Microcontroller Self-Monitoring and Auto Reboot. 

Содержание KBAC-24D

Страница 1: ...G and 3G Models3 5 KBAC 24D 27D 29 29 1P 45 48 217 217S 217F 217SF 416 416S 416F 416SF The information contained in this manual is intended to be accurate However the manufacturer retains the right to...

Страница 2: ...anual Start Selection J3 19 10 4 Motor Frequency Selection J4 and J5 19 10 4 1 Setting the Drive for 50 Hz or 60 Hz Motor Operation J4 and J5 19 10 4 2 Setting the Drive for Two Times the Rated Motor...

Страница 3: ...ection J10 20 32 Switching Frequency and GFCI Selection Third Generation 3G Drives Only J12 20 33 Minimum Speed Trimpot MIN Range 21 34 Maximum Speed Trimpot MAX Range 21 35 Acceleration Trimpot ACCEL...

Страница 4: ...minals L1 L2 L3 AC Line input Rated for 208 230 Volt AC Line input only Rated for 2 HP maximum with 1 phase AC Line input and 3 HP maximum with 3 phase AC Line input KBAC 217 217S 217F 217SF Designed...

Страница 5: ...tilated 3 phase AC induction motors will overheat if used beyond a limited speed range at full torque Therefore it is necessary to reduce motor load as speed is decreased Note Some fan cooled motors c...

Страница 6: ...ided for easy installation of accessories Custom software all models can be factory programmed for applications which require special timing PLC functions and GFCI operation 4 1 STANDARD FEATURES Indu...

Страница 7: ...Specification Factory Setting 115 Volt AC Line Input Voltage Operating Range Volts AC 115 15 208 230 Volt AC Line Input Voltage Operating Range Volts AC 208 15 230 15 400 460 Volt AC Line Input Voltag...

Страница 8: ...selection See Section 10 4 on page 19 7 Jumper J12 Switching Frequency and GFCI selection Third Generation 3G drives only See Section 10 11 on page 20 8 Jumper J6 Adjustable Boost selection See Sectio...

Страница 9: ...er J4 Frequency Multiplier selection See Section 10 4 on page 19 8 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 20 9 Jumper J5 Motor Frequency selection See Section 10 4 on...

Страница 10: ...10 5 on page 20 7 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 19 8 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 20 9 Jumper J5 Motor Frequency selecti...

Страница 11: ...IN Acceleration ACCEL Deceleration DECEL DC Injection Brake DECEL Boost BOOST Current Limit CL Jog JOG Slip Compensation COMP See Section 12 on pages 21 and 22 8 Selectable Jumpers Motor Horsepower J2...

Страница 12: ...are should be taken to avoid extreme hazardous locations where physical damage can occur When mounting the drive in an enclosure the enclosure should be large enough to allow for proper heat dissipati...

Страница 13: ...KBAC SERIES INSTALLATION AND OPERATION MANUAL 13 FIGURE 9 KBAC 27D 29 29 1P 45 48 MECHANICAL SPECIFICATIONS Inches mm Tighten these screws in the sequence shown to 12 in lbs 14 kg cm...

Страница 14: ...KBAC SERIES INSTALLATION AND OPERATION MANUAL 14 FIGURE 10 KBAC 217 217S 217F 217SF 416 416S 416F 416SF MECHANICAL SPECIFICATIONS Inches mm...

Страница 15: ...e cover making sure that the wires do not get caught or crimped as the cover is closed Tighten the four screws so that the gasket is slightly compressed The recommended tightening torque is 12 in lbs...

Страница 16: ...Ground Wire Earth to the Green Ground Screw The Ground Screws are located next to Terminal Block TB1 See Figures 11 13 on pages 15 and 16 7 4 REMOTE MAIN SPEED POTENTIOMETER CONNECTION The drive is su...

Страница 17: ...iometer setting when the AC Line is applied 7 7 VOLTAGE FOLLOWING CONNECTIONS An isolated 0 5 Volt DC analog signal input can also be used to control motor speed in lieu of the Main Speed Potentiomete...

Страница 18: ...tic ramping then the hi pot output must be manually increased to the test voltage and then manually reduced to zero This procedure must be followed for each machine to be tested A suggested hi pot tes...

Страница 19: ...econds the drive will shut down and then ride through and automatically return to the set frequency See Figure 24 If Jumper J3 is set to the M position the drive will have to be manually restarted for...

Страница 20: ...Y Jumper J12 is factory set to the 8K position for a switching frequency at the motor of 8 kHz For 12 kHz switching frequency set Jumper J12 to the 12K position This jumper also allows the drive to be...

Страница 21: ...ot exercised The Safety Warnings on page 5 must be read and understood before proceeding 12 1 MINIMUM SPEED TRIMPOT MIN Sets the minimum speed of the motor The MIN Trimpot is factory set to 0 of frequ...

Страница 22: ...or is properly protected with the I2 t feature it is required that the CL Trimpot be set for 160 of the motor nameplate rated current as described below 12 8 BOOST TRIMPOT BOOST The drive is factory s...

Страница 23: ...urce and the drive Mounts on the drive s PC board with four snap ins 2G 9600C 9600C 9600C 9600C 9600C 9600C 3G1 8890 8890 8890 8890 8890 8890 8890 Auto Manual Switch Kit When used with the Signal Isol...

Страница 24: ...on and removal inconvenience or consequential damage including injury to any person caused by items of our manufacture or sale Some states do not allow certain exclusions or limitations found in this...

Отзывы: